Technical data

Solar Inverter NT 2600

Recommended PV generator power

Rated input power
Stand-by consumption
Night-time consumption
AC energy generated from
Nominal voltage
U

MPP

voltage range

Open-circuit voltage
Switch-on voltage
Switch-off voltage
Maximum current
Nominal current
Number of inputs

Maximum efficiency
European efficiency (weighted)
HERIC

®

topology

Rated continuous output power Pn
Maximum power Pp
Nominal frequency
Grid voltage
Grid voltage tolerance range
Nominal current
Max. current
Distortion factor at Pn
Reactive power factor (cos phi)
Output current

Model

1500 bis 2750 W

2300 W
9 W
< 0.005 W
15 W
400 V
350 ≤ U

MPP

≤ 650 V

750 V
410 V
340 V
7 A
5.75 A
2 (with adapter: 4)

97 per cent
96.5 per cent
yes

2200 W
2200 W
50 Hz +/- 0.2
230 V
- 20 to +15 per cent
9.6 A
9.6 A
< 3 per cent
~ 1
sinusoidal

DC

AC