Buccaneer gt, falcon gte, 1 technical specifications of combination boilers – IDEAL INDUSTRIES BUC5034 User Manual
Page 3
Buccaneer GT, Falcon GTE
- Installation, Assembly & Servicing
3
1.1 Technical Specifications of Combination Boilers
Boiler:
Maximum operating pressure
:
4 bar
Maximum operating temperature
:
100ºC
Maximum safety temperature of
boiler (as per TRD 702)
:
120ºC
Boiler thermostat setting
:
30 - 85ºC
Safety thermostat setting
:
110ºC
MLS Calorifier:
Primary circuit (heating water)
- Maximum operating temperature
:
95ºC
- Maximum operating pressure
:
12 bar
Secondary circuit (domestic hot water)
- Maximum operating temperature
:
95ºC
- Maximum operating pressure
:
10 bar
Bucaneer GT - Domestic Hot Water Production
3
4
5
MLS tank capacity
litres
150
150
150
Continuous flow rate (1) (2)
litres/h
640
780
780
Maximum flow rate over 10mn (1) (2) (3)
litres/10mn
235
260
260
Weight (Boiler and tank)
kg
228
256
284
Falcon GTE - Domestic Hot Water Production
4 (150/250)
5 (150/250)
MLS tank capacity
litres
150/250
150/250
Continuous flow rate (1) (2)
litres/h
780/950
780/950
Maximum flow rate over 10mn (1) (2) (3)
litres/10mn
260/380
260/380
Weight (boiler and tank) 150 litre
kg
354
395.5
Weight (boiler and tank) 250 litre
kg
384
425.5
(1) Domestic cold water at 10ºC - Domestic hot water at 45ºC - Primary at 80ºC
(2) Storage temperature : 60ºC
(3) Boiler temperature
: 80ºC - Ambient temperature
:
20ºC
Tank Details
Note: With IDEAL boilers, the setting limits the temperature of the primary circuit at the beginning to 75ºC (adjustment is possible from
50ºC to 95ºC).
Tank Type
MLS 150/III
MLS 250/II
Primary circuit (central heating water)
Water capacity of coil
litres
5.9
7.2
Exchange surface of coil
m
2
0.92
1.2
Secondary circuit (sanitary water)
Water capacity
litres
150
250
Delivery weight
kg
100
130