COMMERCIAL 100 kW

KW RATING

100

ENGINE SIZE

6.8 Liter V-10

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

KW

AMP

CB Size

120/240V, single phase, 1.0 pf

100 LP / 98 NG

416.6 LP / 408.3 NG

450

120/208V, 3-phase, 0.8 pf

100 LP / 98 NG

347.4 LP / 340.4 NG

400

120/240V, 3-phase, 0.8 pf

100 LP / 98 NG

301 LP / 295 NG

350

277/480V, 3-phase, 0.8 pf

100 LP / 98 NG

150.5 LP / 147.5 NG

175

GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208V & 240V 3-phase

190

480V

3-phase

225

ENGINE FUEL CONSUMPTION

(Natural Gas) (Propane)

Natural Gas

Propane

(ft3/hr.) (gal/hr.)

cu

ft/hr

Exercise

cycle

130

1.42

52.3

25% of rated load

371

4.06

149.4

50% of rated load

713

7.81

287.4

75% of rated load

994

10.88

400.4

100% of rated load

1260

13.80

507.8


ENGINE COOLING
Air

flow

(inlet air including alternator and combustion air)

ft3/min 5,500

System coolant capacity

US gal.

4.5

Heat rejection to coolant

BTU/hr.

342,000

Max. operating air temp. on radiator

°C (°F)

60 (150)

Max. ambient temperature

°C (°F)

50 (140)

COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz

cfm

262


SOUND EMISSIONS IN DBA
db(A) @ 23 feet in exercise mode

61

db(A) @ 23 feet at normal operating load

72


EXHAUST
Exhaust flow at rated output 60 Hz

cfm 888

Exhaust temp. at muffler outlet

°F

960

ENGINE PARAMETERS
Rated synchronous RPM

60 Hz

2300

HP at rated KW

60 Hz

168

POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature

Deration

3% for every 10 °C above - °C

25

1.65% for every 10 °F above - °F

77

Altitude

Deration

1% for every 100 m above - m

183

3% for every 1000 ft. above - ft.

600

OPERATING DATA

COMMERCIAL 100 kW

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility
source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and
specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power
and condition, etc.