PRODUCT DESIGN

Filters:

Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or
CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty.

This furnace has provisions for the installation of return air filters at the side and/or bottom return. The furnace will
accommodate the following filter sizes depending on cabinet size:

Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in
the duct system such as a central return.

Upflow Filters

Disposable Minimum Filter Area (in

2

)

[Based on a 300 ft/min filter face velocity]

*Minimum filter area dictated by heating airflow requirement.

Permanent Minimum Filter Area (in

2

)

[Based on 600 ft/min filter face velocity]

*Minimum filter area dictated by heating airflow requirement.

600

800

1000

1200

1400

1600

2000

0453BXA*

194*

194*

240

288

---

---

---

0703BXA*

---

324*

324*

324*

336

---

---

0704CXA*

---

---

291*

291*

336

384

---

0904CXA*

---

---

432*

432*

432*

432*

---

0905DXA*

---

---

---

388*

388*

388*

480

1155DXA*

---

---

---

486*

486*

486*

486*

In

p

u

t_

_A

ir

fl

o

w

COOLING AIRFLOW REQUIREMENT (CFM)

600

800

1000

1200

1400

1600

2000

0453BXA*

388*

388*

480

576

---

---

---

0703BXA*

---

647*

647*

647*

672

---

---

0704CXA*

---

---

583*

583*

672

768

---

0904CXA*

---

---

863*

863*

863*

863*

---

0905DXA*

---

---

---

777*

777*

777*

960

1155DXA*

---

---

---

971*

971*

971*

971*

COOLING AIRFLOW REQUIREMENT (CFM)

Input__A

ir

flow

Cabinet

Width

(in.)

Nominal

Filter Size

(in.)

Approx.

Flow Area

(in

2

)

Cabinet

Width

(in.)

Nominal

Filter Size

(in.)

Approx.

Flow Area

(in

2

)

All

16 x 25 x 1

400

17-1/2

14 x 25 x 1

350

21

16 x 25 x 1

400

24-1/2

20 x 25 x 1

500

BOTTOM RETURN

(1)

SIDE RETURN

(1) Flanges on bottom return must be unfolded

Thermostats: