8. 115 volts ac duplex receptacle, 9. electrical service guide – Hobart Welding Products 300 DC User Manual
Page 17

OM-318 Page 13
2-8.
115 Volts AC Duplex Receptacle
Ref. ST-152 973-A
Y
Turn Off power before con-
necting to receptacle.
1
115 V AC Receptacle
Receptacle is protected from over-
load by circuit breaker CB1 (see
Section 4-2).
Power output is shared between
this receptacle and the Remote 14
receptacle (see Section 2-7).
1
2-9.
Electrical Service Guide
60 Hz
50 Hz
Input Voltage
200
230
460
575
220
380
415
Input Amperes At Rated Output
105
91
46
36
88
51
47
Max Recommended Standard Fuse Or Circuit Breaker Rating In
Amperes
Circuit Breaker
1
, Time-Delay
2
125
110
50
45
110
60
50
Normal Operating
3
150
125
70
50
125
80
70
Min Input Conductor Size In AWG/Kcmil
4
6
8
10
6
8
8
Max Recommended Input Conductor Length In Feet (Meters)
116
(35)
103
(31)
271
(83)
284
(87)
99
(30)
194
(59)
232
(71)
Min Grounding Conductor Size In AWG/Kcmil
6
6
8
10
6
8
8
Reference: 1999 National Electrical Code (NEC)
1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).