beautypg.com

Specifications – Honeywell 500 User Manual

Page 2

background image

CLASS 500 ADVANCED KWH/DEMAND METER

62-0304—05

2

SPECIFICATIONS

Input Voltage Configuration:

3-wire (Delta) or 4-wire (WYE)

Mains Voltage Input:

Up to 600 VAC RMS available

Input Power:

6 VA maximum rating

Current Sensor Rating:

Up to 3200 Amp RMS AC available

Power Factor:

.5 leading or lagging

Line Frequency:

50-60 Hz

Metering Accuracy:

Certified to ANSI C12.16

Voltage Operating Range:

+/-10% of rated load

Temperature Range (Class 500):

NEMA 4 (Outdoor) Housing: -20 ºC to +70 ºC

NEMA 12 (Indoor) Housing: -20 ºC to +50 ºC

Relative Humidity Range:

0-95% non-condensing

Altitude:

2000 meters maximum

Voltage Overload:

+25% continuously; +100% for 20 cycles

Current Sensor Overload:

100% for 1 minute without damaging meter

Pollution Degree:

Degree 2 In accordance with IEC 664

Installation (Overvoltage) Category:

Category III

Measurement Category:

Category III

Outdoor Housing Rating (Model numbers with an R at the

end):

NEMA 4

Indoor Housing Rating (Model numbers without an R at

the end):

NEMA 12

Display Readout:

KWh accumulated

Standard Ranges:

(3 or 4 Wire) 120/208-240V: 100,200,400,800,1600, 3200

Amp

(3 or 4 Wire) 277/480V: 100,200,400,800,1600, 3200 Amp

(4 Wire) 346/600 V: 100,200,400,800,1600, 3200 Amp

RS485 Serial Communication Interface:

Cable Specifications: UL listed/rated telephone cord,

4 conductor, 300VAC, stranded conductors, 22-26 AWG.

Input/Output Voltage: Ground isolated +/-5.4 VDC

Cable Connector: RJ-11 connector

Ckt Input Isolation: 5.3 KVAC

Max Cable Distance: 4000 feet

Max Network Nodes: Maximum cabling nodes 52

including master node

Baud Rate: 9600

Communications Options:

RS232/RS485 (Standard) (Requires E-Mon Energy.)

Telephone Modem (Requires E-Mon Energy.)

Ethernet (Requires E-Mon Energy.)

Modbus RTU or TCP/IP (Requires third-party EMS/BMS.)

BACnet IP or MS/TP (Requires third-party EMS/BMS.)

LONworks TP (Twisted Pair) (Requires third-party EMS/

BMS.)

Recommended In-Line Fuse:

Manufacturer: Littelfuse

Mfg Part No.: KLDR.100

Rating:100 mA, time delay. 600 VAC cartridge fuse

Battery Cell:

Description: Non-rechargeable cell used for memory

retention.

Manufacturer: Eagle-picher

Mfg Part No.: LTC-3PN

Working Voltage: 3.5 Vdc

Current Capacity: 350 mAHr

Electrolyte: Lithium thionyl nitrate