Start-up Checklist

Date of Start-up

Location

CONDENSING UNIT

MODEL #

ELECTRICAL

• Check Compressor Amps for COOLER and

FREEZER compressors. Should match

nameplate.

YES

NO

PIPING

• Is suction line trapped at the Cooler?

YES

NO

• Is suction line trapped at the Freezer?

YES

NO

DRAIN LINES

• Are drain lines sloped properly?

YES

NO

• Is drain line trapped outside the Cooler?

YES

NO

• Is drain line trapped outside the Freezer?

YES

NO

• Is heat tape wrapped along entire length of

the drain line in the Freezer?

YES

NO

• Is heat tape plugged in and heating the drain

line?

YES

NO

INSULATION

• Are Liquid lines fully insulated?

YES

NO

• Are Suction lines fully insulated?

YES

NO

SYSTEM CHECKS

• Check Compressor Superheat for the

COOLER (Should be between 20°F. & 30°F.)

YES

NO

• Check Compressor Superheat for the

FREEZER (Should be between 20°F. & 30°F.)

YES

NO

•Force unit into a Defrost Check heater amps.

Should match nameplate amps.

YES

NO

• Check LPS Time Delay Relays. Should be

set at 1 minute for both the COOLER and

FREEZER.

YES

NO

• Check Low Pressure Switch on FREEZER. Should be set

at 0 psig Cut-out/10 psig Cut-in.

YES

NO

• Did FREEZER and COOLER cycle off on LPS at Set-point

Temperature?

YES

NO

• Is the sight glass free of bubbles?

YES

NO

• Are the COOLER and FREEZER fans at proper speeds?

YES

NO

• Check system for refrigerant leaks. Are there any

leaks on the COOLER, FREEZER, CONDENSING UNIT or

INTERCONNECTING PIPING?

YES

NO

• Check system piping for unusual vibration or noise. Is

there any unusual vibration or noise on the COOLER,

FREEZER, CONDENSING UNIT or INTERCONNECTING

PIPING?

YES

NO