beautypg.com

Installation, When installing this product, Location – Honeywell ML6131 User Manual

Page 3: Mounting, Warning, Caution

background image

ML6131 DIRECT COUPLED ACTUATOR

3

63-2498—2

Fig. 1. Approximate dimensions of ML6131

Direct Coupled Actuator in in. (mm).

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.

2.

Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.

3.

Installer must be a trained, experienced service
technician.

4.

After installation is complete, check out product
operation as provided in these instructions.

IMPORTANT

All wiring must agree with applicable codes,
ordinances and regulations.

WARNING

Explosion Hazard.
A spark from the actuator or attached accessories
can result in serious injury or death.
Install the actuator in areas free of escaping gas and
other explosive vapors.

CAUTION

Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect all power supplies before installation.
Actuators with auxiliary switches can have more than
one disconnect.

CAUTION

Actuator Damage Hazard.
Deteriorating vapors and acid fumes can damage
the actuator metal parts.
Install actuator in areas free of acid fumes and
deteriorating vapors.

Location

Choose a location for the actuator that allows enough
clearance for mounting accessories and for servicing.

Mounting

These actuators are designed to open a damper or valve by
driving the shaft in either the clockwise (cw)

or

counterclockwise (ccw)

direction. The actuator has a

mounting tab on the bottom that secures it to a damper box or
valve linkage. When mounted correctly, this tab allows the
actuator to float without rotating relative to the shaft. The tab is
sized for 1/4 in. self-tapping sheet metal screws (not
included).

CAUTION

Equipment Damage Hazard.
Tightly securing mounting tab to damper housing
can damage actuator.
Once mounted, the actuator must be allowed to float;
do not fully tighten the screw.

These actuators are shipped in the fully clockwise 90° position
as viewed from the end of the damper shaft.

CAUTION

Equipment Damage Hazard.
Mounting actuator unevenly with damper housing
can damage actuator.
Mount actuator flush with damper housing or add
spacer between mounting tab and damper box
housing (see Fig. 2).

Fig. 2. Mounting actuator to VAV box when

actuator is not flush with box.

1 (25)

M18016

CW

COM

CCW

OPTIONAL
AUXILIARY
SWITCH

11/16

(18)

3-3/8 (86)

4-1/4
(108)

4-7/8
(123)

2-7/8 (73)

1-11/16

(42)

1/8

(3)

1-5/16

(33)

7/8

(22)

2-1/2 (64)

ADD SPACER BETWEEN
DAMPER BOX AND TAB

DAMPER
SHAFT

ML6131

VAV BOX HOUSING

M4449