beautypg.com

Finishing – Heat & Glo Fireplace Heat & Glo Cosmo-130 User Manual

Page 28

background image

Heat & Glo • Cosmo-I30, Cosmo-I35 • 2239-900 Rev. H • 1/11

28

11

Finishing

A. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear-

ances to combustibles as specifi ed. Framing or fi nishing

material closer than the minimums listed must be construct-

ed entirely of noncombustible materials (i.e., steel studs,

concrete board, etc).
Clearance to combustible material under the insert is 1/4

inch (6 mm). Clearance from top of fi replace opening for

combustibles extending 12 inches max. is 12 inches.
• Use leveling legs to raise insert minimum 1/4 inch (6 mm)

above combustible material or outer wrap of factory built

fi rebox.

Combustible facings must not extend behind the insert

surround. For non-combustible material specifi cations

refer to section 1.E.

Figure 11.1 Clearances to Mantels or other Combustibles

above Appliance

12 IN. MIN.

12 IN. MAX.

EXISTING NON-COMBUSTIBLE FACING