Page 17

background image

16

VP 30

Secure the elevation as high as possible

(approx. 100 mm)

A downhill grade of

1/100 or more

Drain hose

Joint for VP 25

(Local procurement)

600

(Maximum local drain up dimension)

Right overhead

290~325mm

Attached drain hose clamp

Drain piping

Main unit

Drain situation can be checked with transparent socket

Remove grommet.

Make sure to install

it back after test.

Insert water supply hose

for 20 mm ~ 30 mm to

supply water.

(Insert hose facing

toward bottom.)

Pour water into a convex joint.

When constructing drain piping for several units, position the

common pipe about 100 mm below the drain outlet of each
unit as shown in the sketch. Use VP-30(11/4") or thicker pipe

for this purpose.
Be sure to provide heat insulation to hard PVC pipes of indoor

placement.
Do not ever provide an air vent.

The height of the drain head can be elevated up to a point 500
mm above the ceiling, and when an obstacle exists in the
ceiling space, elevate the piping to avoid the obstacle using

an elbow or corresponding gadget. When doing this, if the

stretch for the needed height is higher than 500 mm, the back-
flow quantity of drain at the event of interruption of the

operation gets too much and it may cause overflow at the
drain pan. Therefore, make the height of the drain pipe within

the distance given in the sketch below.

Avoid positioning the drain piping outlet at a place where
generation of odor may be stimulated. Do not lead the drain

piping direct into a sewer from where sulfur gas may generate.

Drainage Test

Conduct a drainage test after completion of the electrical work.
During the trial, make sure that drain flows properly through the piping and that no water leaks
from connections.

In case of a new building, conduct the test before it is furnished with the ceiling.
Be sure to conduct this test even when the unit is installed in the heating season.

Procedures

Supply about 1000 cc of water to the unit through the air outlet using a feed water pump.

Check the drain while cooling operation.

(d)

(e)

(f)

(h)

(g)

1
2

3

4

1
2

(In the electrical work has not been completed,

connect a convex joint in the drain pipe connection
to provide a water inlet. Then, check if water
leaks from the piping system and that drain flows
through the drain pipe normally.)

Installation Manual For Indoor Unit