beautypg.com

Hubbell ST User Manual

Page 14

background image

14

3. Install the combination temperature and pressure safety relief valve in the tapping provided.

Note that this is required by law for safety considerations.

Outlet to floor drain

Install into provided tapping



Manual Release
Lever



Temperature Probe

4. Install a relief valve overflow pipe to a nearby floor drain. CAUTION: No valve of any type

should be installed between the relief valve and tank or in the drain line.


HOOK-UP OF AIR AND WATER OPERATED CONTROLS

1. Most air or water operated valves on Hubbell water heaters are controlled by Powers

Accritem. Occasionally, a Robertshaw Fultrol is furnished which operates identically to the
Powers control except supply and output connections are reversed in location. Controls are
normally mounted on the back side of the tank shell.