beautypg.com

Wiring, Warning, Using with preheated oil – Honeywell PRESSURETROL L404T User Manual

Page 5: L404f,t,v pressuretrol, Controllers

background image

L404F,T,V PRESSURETROL

®

CONTROLLERS

5

71-2429—06

Fig. 3. Typical locations of pressure controllers in an oil burner system.

Fig. 4. Mounting an oil pressure controller

directly on the main pipe.

Using with Preheated Oil

When used with preheated oil, a siphon loop must always be

connected between the controller and the main pipe (see Fig.

5) to provide thermal buffering.

Fig. 5. Mounting of a siphon loop, with approximate

dimensions in in. (mm).

WIRING

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or property damage.

Disconnect the power supply before beginning wiring.

More than one power supply disconnect may be

required.

All wiring must comply with applicable codes and ordinances.

All models have terminals (on the MicroSwitch

®

snap-acting

switch) inside the cover and knockouts for conduit and cable.

Refer to manufacturer installation and wiring instructions, if

available, and to typical hookups shown in Fig. 6 to 10.

Fig. 6. L404F in low voltage relay circuit.

MAIN

OIL

LINE

TO OIL

BURNER

ATOMIZER

ATOMIZING MEDIUM

(AIR OR STEAM)

MANUAL

SHUTOFF

VALVE

LOW OIL

PRESSURE

CONTROLLER

HIGH OIL

PRESSURE

CONTROLLER

RECIRCULATING

VALVE AND SAFETY

SHUTOFF VALVE

OIL

PUMP WITH

PRESSURE RELIEF

LOW OIL

TEMPERATURE

STRAINER

MANUAL

SHUTOFF

VALVE

M17861

OIL PRESSURE

CONTROLLER

(AT RIGHT

ANGLES TO THE

MAIN PIPE LINE)

PIPE

WRENCH

HEXAGONAL

FITTING

MAIN PIPE LINE

M17860

MAIN TEE

(TURN TO LEVEL

THE CONTROLLER)

PIPE NIPPLE

4-1/2

TO

5-1/2

(114 TO

140)

PREHEATED OIL SUPPLY LINE

SIPHON LOOP

TEE

OIL PRESSURE

CONTROLLER

M23886

1

1 1/4 INCH PIPE WITH 1/4-18 NPT EXTERNAL THREADS ON

BOTH ENDS AND 2-1/4 IN. (57 MM) DIAMETER LOOP.

M19637A

1

1

2

2

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION

AS REQUIRED.

AS SHOWN, SWITCH OPENS ON PRESSURE RISE. REVERSE

ACTING (MAKE ON PRESSURE RISE) UNITS ARE WIRED TO

R-W TERMINALS AND TERMINAL B IS OMITTED.

L404F PRESSURETROL

24 VOLT

POWER

SUPPLY

R
W
B

L1

(HOT)

POWER

SUPPLY

24 VOLT RELAY

L2

This manual is related to the following products: