beautypg.com

Installation procedure – haier AD212XLEAA User Manual

Page 20

background image

18

Supplementary refrigerant

The refrigerant supplementation shall be as specified in the installation instructions
attached with the outdoor unit. The added refrigerant shall be R22.
The adding procedure shall be aided with a measuring meter
for a specified amount of supplemented refrigerant

Requirement

Overfilling or underfilling of refrigerant will cause compressor
fault. The amount of the added refrigerant shall be as specified
in the instructions.

Connection of refrigerant pipe

The connection of indoor unit pipes must use double spanners.
The installing torque shall be as given in the following table.

Double-spanner
operation

Connecting pipe

O.D.(mm)

я6.35

я9.52

я12.70

я15.88

Installing torque

(N-m)

11.8 (1.2kgf-m)

24.5 (2.5kgf-m)

49.0 (5.0 kgf-m)

78.4 (8.0 kgf-m)

Increased installing

torque (N-m)

13.7 (1.4 kgf-m)

29.4 (3.0 kgf-m)

53.9 (5.5 kgf-m)

98.0 (10.0 kgf-m)

Conduct flared connection work to connect all refrigerant pipes.

Pipe cutting and expanding

If the pipe is too long or the flare is damaged, it needs to be cut or expanded.

Pipe expander

Pipe expansion dimensions as follows:

A

Allowable pipe length and drop

These parameters differ according to the outdoor unit. See the instruction manual attached
with the outdoor unit for details.

1. Pipe cutting 2. Removing burrs 3.Insertion nut 4. Pipe expansion

Installation Procedure

Slope Damage Bur Partial Overlong

Correct

Incorrect

6.35 mm (1/4

"

) 0.8 ~ 1.5

9.52 mm (3/8

"

) 1.0 ~ 1.8

12.7 mm (1/2

"

) 1.2 ~ 2.0

15.88 mm (5/8

"

) 1.4 ~ 2.2

Pipe diameter

ÿ

Size A (mm)

This manual is related to the following products: