INSTALLATION INSTRUCTIONS

69-1481-1

T8411R Electronic

Heat Pump Thermostat

The T8411R Heat Pump Thermostat provides 24V

control of two-stage heating and one-stage cooling heat
pump system with manual changeover from heat to cool.

First stage heating and cooling cycle rates are fixed at
3 cph. Second stage heating cycle rate is selectable at

3, 4, 5, 6, or 9 cph. Temperature indication can be set for
°F or °C.

The T8411R Heat Pump Thermostat is powered directly

from the system transformer. Batteries are not required
because setpoints are held permanently by non-volatile

memory.

The T8411R TRADELINE® model includes a thermostat,
wallplate (for wiring and mounting thermostat), and

owner’s guide. A 7 3/8 in. x 5 3/4 in. (188mm x146 mm)
decorator cover plate (for covering wall marks) is

available separately. Order Honeywell part no. 209649A
(taupe color).

MERCURY NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do not place your old

control in the trash.

Contact your local waste management authority
for instructions regarding recycling and the

proper disposal of an old control containing
mercury in a sealed tube.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a hazard-
ous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for

your application.

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out product

operation as provided in these instructions.

CAUTION

Electrical Shock or Equipment Damage
Hazard.

Can shock individuals or short equipment
circuitry.

Disconnect power supply before installation.

Location

Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.

See Fig. 1. Do not install the thermostat where it can be
affected by:

— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.

— radiant heat from the sun or appliances.
— concealed pipes and chimneys.

— unheated (uncooled) areas such as an outside wall

behind the thermostat.

This thermostat is a precision instrument and was

carefully adjusted at the factory. Handle it carefully.

Mounting Wallplate to Wall

IMPORTANT

Level only for appearance. The thermostat func-
tions normally even when not level.

Mount wallplate, T8411R and the screws provided (see

Fig. 2) as follows:

1. Place the wallplate at the desired location on the

wall.

2. Use a pencil to mark the mounting holes.

3. Remove the wallplate from the wall and drill two

3/16 in. holes in the wall (if drywall) or two 7/32 in.

holes for firmer material such as plaster or wood.

4. Gently tap the anchors (provided) into the holes

until flush with the wall.

5. Position the wallplate over the holes.

6. Pull the thermostat wire through the wallplate

entrance hole.

7. Fasten the wallplate to the wall using the anchors

and screws provided.