EXCEL 500/600 INSTALLATION INSTRUCTIONS

COMMUNICATIONS

L

ON

W

ORKS

Bus Wiring

Connection between the Distributed I/O modules and the
CPU are made from the L

ON

W

ORKS

connector module

XSL511. The L

ON

W

ORKS

bus is a 78-kilobit serial link that

uses transformer isolation so that the bus wiring does not
have a polarity; that is, it is not important which of the two
L

ON

W

ORKS

bus terminals are connected to each wire of the

twisted pair.
The L

ON

W

ORKS

bus can be wired in daisy chain, star, loop or

any combination thereof as long as the maximum wire length
requirements given below are met. The recommended
configuration is a daisy chain with two bus terminations. This
layout allows for maximum L

ON

W

ORKS

bus length, and its

simple structure presents the least number of possible
problems, particularly when adding on to an existing bus.

Table 16. Doubly-terminated bus specifications

Cable type

Max. bus length

Belden 85102

2700 m (8900 ft)

Belden 8471

2700 m (8900 ft)

Level IV, 22 AWG

1400 m (4600 ft)

JY (St) Y 2x2x0.8

900 m (3000 ft)

TIA568A Categ. 5 24AWG, twisted pair

900 m (3000 ft)

NOTES: The cable types listed above are as recommended

by Echelon in their FTT-10A User Guide. The cable
recommended by Honeywell is the level IV, 22
AWG, solid core, nonshielded cable. Belden part
numbers are 9H2201504 (plenum) and 9D220150

IMPORTANT

Do not use different wire types or gauges on the
same L

ON

W

ORKS

network segment. The step

change in line impedance characteristics would
cause unpredictable reflections on the bus.

NOTE: In the event that the limit on the total wire length is

exceeded, then FTT physical layer repeaters
(FTT 10A) can be added to interconnect segments
and increase the overall length by an amount equal
to the original specification for that cable type and
bus type for each repeater used. For example,
adding repeaters for a doubly-terminated bus using
JY (St) Y 2x2x0.8 cable increases the maximum
length 3000 ft (900 m) for each repeater.

On the Excel 500-XCL5010 controller, the L

ON

W

ORKS

bus

connections are located on the communication module as
shown in Fig. 78:

LON SERVICE BUTTON

POWER, GRN
LON SERVICE, RED

LEDs

C-BUS TxD, YEL
C-BUS RxD, YEL
RESERVED

C-BUS
TERMINATION
SWITCH

1 2 3

4 5 6

LON

C-BUS

(non-plenum).

BUS

IMPORTANT

A1 A2

NO

T

US

E

D

SH

IE

L

D

C + C ­

00

00

01

24

It is recommended that ferrules not be used to
terminate stranded wires to be inserted in the
Distributed I/O Terminal blocks spring-clamp
terminals.

The FTT specification includes two components that must be
met for proper system operation. The distance from each
transceiver to all other transceivers and to the termination
must not exceed the maximum node-to-node distance. If
multiple paths exists, the maximum total wire length is the
total amount of wire used.

Table 17. Free topology (singly-terminated) specifications

Cable type

Max. node-to-

node distance

Max. total wire

length

Belden 85102

1650 ft (500m)

1650 ft (500m)

Belden 8471

1300 ft (400m)

1650 ft (500m)

Level IV, 22AWG

1300 ft (400m)

1650 ft (500m)

JY (St) Y 2x2x0.8

1050 ft (320m)

1650 ft (500m)

TIA568A Category 5
24AWG, twisted pair

825 ft (250m)

1500 ft (450m)

Fig. 78. Excel 500-XCL5010 communication module

L

ON

W

ORKS

Bus Termination

Depending upon the configuration, either one or two
termination modules are required for terminating a L

ON

W

ORKS

bus with FTT devices on it. The following two different
L

ON

W

ORKS

termination units are available for this purpose:

• 209541B

L

ON

W

ORKS

Bus Termination Module (see Fig.

79 and Fig. 80) and

• XAL-Term

L

ON

W

ORKS

connection and termination

module (see Fig. 81), which can be mounted on DIN rails
and in fuse boxes.

Fig. 79. Termination Module 209541B connections for

doubly-terminated FTT network

EN1R-1047GE51 RR0902