beautypg.com

Dimensions – AdobeAir MD628 User Manual

Page 6

background image

DIMENSIONS

Certifi ed Air Delivery CFM at Various External Static Pressures

Inches Water Gauge. AMCA Licensed Ratings.

MD/MS 524 or UD/US 960 Sheave Selection

Motor HP

Browning Bore

Blower RPM / Sheave Turns Open

MasterCool

Part #

5

4 ½

4

3 ½

3

2 ½

2

1 ½

1

½

0

Package #

Single Phase Motor Blower RPM @ 1725 Motor RPM / Sheave Turns Open
¾, 1

1VL34

5

/

8

252 265 279 292 305 318 332 345 358 372 385 EL114

¾, 1

1VL40

5

/

8

318 332 345 358 372 385 398 411 425 438 451 EL110

1½, 2

1VL40

7

/

8

318 332 345 358 372 385 398 411 425 438 451 EL112

¾, 1

1VL44

5

/

8

372 385 398 411 425 438 451 464 478 491 504 ESH2411

1½, 2

1VL44

7

/

8

372 385 398 411 425 438 451 464 478 491 504 EL685

1½, 2

1VP50

7

/

8

451 464 478 491 504 518 531 544 557 571 584 686

Three Phase Motor Blower RPM @ 1750 Motor RPM / Sheave Turns Open
¾ 1VL34

5

/

8

256 269 283 296 310 323 337 350 363 377 390 EL114

1 1VL34

7

/

8

256 269 283 296 310 323 337 350 363 377 390 EL116

¾ 1VL40

5

/

8

323 337 350 363 377 390 404 417 431 444 458 EL110

1, 1½, 2 1VL40

7

/

8

323 337 350 363 377 390 404 417 431 444 458 EL112

¾ 1VL44

5

/

8

377 390 404 417 431 444 458 471 485 498 512 ESH2411

1, 1½, 2 1VL44

7

/

8

377 390 404 417 431 444 458 471 485 498 512 EL685

3 1VL44

1

1

/

8

377 390 404 417 431 444 458 471 485 498 512 684

1½, 2

1VP50

7

/

8

458 471 485 498 512 525 538 552 565 579 592 686

3 1VP50

1

1

/

8

458 471 485 498 512 525 538 552 565 579 592 685

Shaded Areas: Do not exceed listed RPM, water entrainment may result.

NOT RECOMMENDED

Operating

Belt information

.0

.0

.1

.1

.2

.2

Model

Weight BHP Quantity Down Side Up

CFM RPM

CFM RPM

CFM RPM

524 with DM080 or 960 with UM080 — 8” Media

560

¾

1

AX78 AX80

6390 298

6070 310

5710 320

570

1

1

AX78 AX80

7030 329

6760 339

6420 349

575 1½

1

AX78 AX80

8050 376

7810 385

7530 394

580

2

1

AX78 AX80

8860 414

8640 422

8400 430

590

3

1

AX78 A82*

9050 422

9050 440

9050 459

524 with DM120 or 960 with UM120 — 12” Media

600

¾

1

AX78 AX80

6250 298

5900 309

5550 321

610

1

1

AX78 AX80

6880 328

6560 338

6250 349

615 1½

1

AX78 AX80

7880 376

7600 384

7320 393

620

2

1

AX78 AX80

8670 414

8420 421

8160 429

630

3

1

AX78 A82*

9050 422

9050 439

9050 458

628 with two DM080 or 980 with two UM080 — 8” Media

818 1

1 A95*

A95*

A95 9720

214 9320

224

8650

235

823

1½ 1 A95*

A95*

A95 11130

245 10720

254

10230

263

828 2

1 A95*

A95*

A95 12250

270 11890

278

11460

286

838 3

2 A97

A97

A95 14020

309 13720

316

13350

323

858 5

2 A97

A97

A95 16620

367 16390

371

16080

378

898

2

A100*

A100*

A95

18100

406

18100

418

628 with two DM120 or 980 with two UM120 — 12” Media

908 1

1 A95*

A95*

A95 9680

216 9080

226

8530

237

913

1½ 1 A95*

A95*

A95 11080

248 10540

256

10080

265

918 2

1 A95*

A95*

A95 12190

273 11700

280

11260

288

928 3

2 A97

A97

A95 13950

312 13510

318

13130

325

948 5

2 A97

A97

A95 16540

370 16050

375

15820

380

988

7½ 2 A100*

A100*

A95 18100

406 18100

409

18100

428

*Not supplied: MS524 coolers with a 3 HP motor require the purchase of one A82 belt
(AX78 belt included with unit). MD628 and MS628 coolers with 1, 1

1

2

or 2 HP motor

requires one A95 belt (two A97 belts included with unit). MD628 and MS628 coolers
with 7

1

2

HP motor require two A100 belts (two A97 belts included with unit).

This manual is related to the following products: