Dimensions – AdobeAir MD628 User Manual
Page 6

DIMENSIONS
Certifi ed Air Delivery CFM at Various External Static Pressures
Inches Water Gauge. AMCA Licensed Ratings.
MD/MS 524 or UD/US 960 Sheave Selection
Motor HP
Browning Bore
Blower RPM / Sheave Turns Open
MasterCool
Part #
5
4 ½
4
3 ½
3
2 ½
2
1 ½
1
½
0
Package #
Single Phase Motor Blower RPM @ 1725 Motor RPM / Sheave Turns Open
¾, 1
1VL34
5
/
8
252 265 279 292 305 318 332 345 358 372 385 EL114
¾, 1
1VL40
5
/
8
318 332 345 358 372 385 398 411 425 438 451 EL110
1½, 2
1VL40
7
/
8
318 332 345 358 372 385 398 411 425 438 451 EL112
¾, 1
1VL44
5
/
8
372 385 398 411 425 438 451 464 478 491 504 ESH2411
1½, 2
1VL44
7
/
8
372 385 398 411 425 438 451 464 478 491 504 EL685
1½, 2
1VP50
7
/
8
451 464 478 491 504 518 531 544 557 571 584 686
Three Phase Motor Blower RPM @ 1750 Motor RPM / Sheave Turns Open
¾ 1VL34
5
/
8
256 269 283 296 310 323 337 350 363 377 390 EL114
1 1VL34
7
/
8
256 269 283 296 310 323 337 350 363 377 390 EL116
¾ 1VL40
5
/
8
323 337 350 363 377 390 404 417 431 444 458 EL110
1, 1½, 2 1VL40
7
/
8
323 337 350 363 377 390 404 417 431 444 458 EL112
¾ 1VL44
5
/
8
377 390 404 417 431 444 458 471 485 498 512 ESH2411
1, 1½, 2 1VL44
7
/
8
377 390 404 417 431 444 458 471 485 498 512 EL685
3 1VL44
1
1
/
8
377 390 404 417 431 444 458 471 485 498 512 684
1½, 2
1VP50
7
/
8
458 471 485 498 512 525 538 552 565 579 592 686
3 1VP50
1
1
/
8
458 471 485 498 512 525 538 552 565 579 592 685
Shaded Areas: Do not exceed listed RPM, water entrainment may result.
NOT RECOMMENDED
Operating
Belt information
.0
.0
.1
.1
.2
.2
Model
Weight BHP Quantity Down Side Up
CFM RPM
CFM RPM
CFM RPM
524 with DM080 or 960 with UM080 — 8” Media
560
¾
1
AX78 AX80
6390 298
6070 310
5710 320
570
1
1
AX78 AX80
7030 329
6760 339
6420 349
575 1½
1
AX78 AX80
8050 376
7810 385
7530 394
580
2
1
AX78 AX80
8860 414
8640 422
8400 430
590
3
1
AX78 A82*
9050 422
9050 440
9050 459
524 with DM120 or 960 with UM120 — 12” Media
600
¾
1
AX78 AX80
6250 298
5900 309
5550 321
610
1
1
AX78 AX80
6880 328
6560 338
6250 349
615 1½
1
AX78 AX80
7880 376
7600 384
7320 393
620
2
1
AX78 AX80
8670 414
8420 421
8160 429
630
3
1
AX78 A82*
9050 422
9050 439
9050 458
628 with two DM080 or 980 with two UM080 — 8” Media
818 1
1 A95*
A95*
A95 9720
214 9320
224
8650
235
823
1½ 1 A95*
A95*
A95 11130
245 10720
254
10230
263
828 2
1 A95*
A95*
A95 12250
270 11890
278
11460
286
838 3
2 A97
A97
A95 14020
309 13720
316
13350
323
858 5
2 A97
A97
A95 16620
367 16390
371
16080
378
898
7½
2
A100*
A100*
A95
18100
406
18100
418
628 with two DM120 or 980 with two UM120 — 12” Media
908 1
1 A95*
A95*
A95 9680
216 9080
226
8530
237
913
1½ 1 A95*
A95*
A95 11080
248 10540
256
10080
265
918 2
1 A95*
A95*
A95 12190
273 11700
280
11260
288
928 3
2 A97
A97
A95 13950
312 13510
318
13130
325
948 5
2 A97
A97
A95 16540
370 16050
375
15820
380
988
7½ 2 A100*
A100*
A95 18100
406 18100
409
18100
428
*Not supplied: MS524 coolers with a 3 HP motor require the purchase of one A82 belt
(AX78 belt included with unit). MD628 and MS628 coolers with 1, 1
1
⁄
2
or 2 HP motor
requires one A95 belt (two A97 belts included with unit). MD628 and MS628 coolers
with 7
1
⁄
2
HP motor require two A100 belts (two A97 belts included with unit).