F120 ROOM AIR CLEANING SYSTEM
68-3042-2
2
SPECIFICATIONS
IMPORTANT
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed specifica-
tions. This product is tested and calibrated under
closely controlled conditions, and some minor differ-
ences in performance can be expected if those con-
ditions are changed.
Model:
F120
consists of:
—two filtered return modules with a return grille, prefilter,
and
—either a 99.97% HEPA filter or a 95% DOP filter and
CPZ module;
—four air supply modules with supply grilles;
—a blower module with a two-speed blower, four
recirculating air supply openings, four recirculating air
return openings and an optional exhaust opening;
—75 ft (23m) of six-inch diameter flexible duct; 75 ft (23m)
of eight-inch diameter flexible duct;
—mounting hardware kit consisting of 12 mounting
brackets; 40 ft (12m) of 12-gauge high-tensile strength
wire; six standard T- bar mounts; duct tape;
—seven duct collar straps.
Color:
Blower Housing: Unpainted galvanized steel.
Return and Supply Grilles: Off-white
Electrical Ratings:
a
Off is “O”.
Air Flow Capacity:
a
With exhaust option installed.
b
Purchase filters separately.
Filters:
HEPA: High efficiency particulate air (HEPA) filter is 99.97 per-
cent efficient for 0.3 micron particulates when measured
with Military Standard 282 DOP test.
DOP: Hospital-grade DOP filter is 95 percent efficient for 0.3
micron particulates when measured with Military Standard
282 DOP test.
CPZ: Sorbent modules contain 11 pounds of sorbent. Adsorbs
higher molecular weight hydrocarbons and oxidizes acid
gases and lower molecular weight hydrocarbons.
Ambient Temperature Rating:
Shipping and Storage: -20
°F to +150°F (-29°C to +66°C).
Operating: Ambient temperatures
≥90°F (32°C).
Can tolerate 104
°F (40°C) for brief periods.
Sound Output Rating at 3.3 ft (1m):
High Speed: 52 dBA (below ASHRAE noise criteria (NC)
curve specifications for NC45 over speech recognition fre-
quency range of 500 to 2000 Hz).
Low Speed: 45 dBA (below ASHRAE noise criteria (NC) curve
for NC35 over speech recognition frequency range of 500
to 2000 Hz).
Installation Weight:
Blower Module: 63 lb (28.6 kg).
Supply Module: (4 required): 8 lb (3.6 kg).
Return Module without filter (2 required): 24 lb (10.9 kg).
95% DOP Filter/CPZ Module (2 required): 21 lb (9.5 kg).
99.97% HEPA Filter (2 required): 10 lb (4.5 kg).
Shipping Weight:
F120 with 95% DOP Filter and CPZ Module:
207 lb (94 kg).
F120 with 99.97% HEPA Filter:
182 lb (83 kg).
F120A1015: 152 lb (69 kg).
F120A1007: 70 lb (32 kg).
Dimensions:
See Fig. 1.
120 Vac, 60 Hz
240 Vac, 60 Hz
Fan Speed
a
Fan Speed
a
II (high)
I (low)
II (high)
I (low)
Current (A) 7.0
5.5
3.5
2.8
Power (W) 800
695
800
695
Model
Voltage
Efficiency
Gas, VOC, Odor
Control Module (2)
Air Vol cfm
(cu m/hr)
Air
Vol cfm
(cu m/hr)
a
Particulates at 0.3
micron (DOP Test)
VOC/Odors
(First Pass Average)
F120A 1023 120 Vac 60 Hz
95%
85%
CPZ
900 (1530)
1050 (1780)
F120A 1031 120 Vac 60 Hz
99.97%
—
—
900 (1530
1000
(1700)
F120A 1015 120 Vac 60 Hz
b
b
b
—
—