(THERMAL CONDUCTIVITY) "K" = BTU in./hr. ft

2

°F

TO SUBSTITUTE ALTERNATE INSULATION MATERIAL, YOU NEED TO KNOW THE "K"
FACTOR FOR THAT MATERIAL. TO CALCULATE THE REQUIRED THICKNESS FOR THE
ALTERNATE MATERIAL USE THE FOLLOWING FORMULA:

K ALT.

.43

EXAMPLE:“K” OF BRICK = 5

5

.43

A hearth extension must be installed with all fire-
places. It is to protect the combustible floor in front of
the fireplace from both radiant heat and sparks.

The construction of and materials used for a factory-
built hearth extension are shown in Figure 5.

A hearth extension of this construction may be cov-
ered with any non-combustible decorative material
and may have a maximum thickness of 6" for the
BW36 and 3” for the BW36C. Seal gaps between the
hearth extension and the front of the fireplace with a
non-combustible sealant.

3. HEARTH EXTENSIONS.

4-00

10

30491D

Figure 5

Factory-Built Hearth Extension

Figure 6

Hearth Extension

EXAMPLES OF INSULATION

USG MICORE CV230

1/2"

0.43

REQUIRED

THICKNESS

K VALUE

x .5 = THICKNESS OF ALTERNATE MAT. (INCHES)

x .5 = 5.81 IN. OF BRICK.

BW36 SERIES WOODBURNING FIREPLACE

NON-COMBUSTIBLE
DECORATIVE MATERIAL

HX3 FACTORY-BUILT
HEARTH EXTENSION

HEARTH SEALING STRIP

GAP (SEAL WITH NON-COMBUSTIBLE SEALANT)

BLACK FIREPLACE BOTTOM

BW36-6"

BW36C-3"

1

/

2

"

52"

16"

NON-COMBUSTIBLE DECORATIVE
COVERING OR .018 MIN. SHEET METAL

INSULATION MIN. R VALUE 1.16

WARNING!

HEARTH EXTENSIONS ARE TO BE INSTALLED ONLY AS ILLUSTRATED

TO PREVENT HIGH TEMPERATURES FROM OCCURRING ON CON-

CEALED COMBUSTIBLE MATERIALS. HEARTH SEALING STRIPS PRE-

VENT BURNING OR HOT PARTICLES FROM INADVERTENTLY FALLING

DIRECTLY ON COMBUSTIBLE SURFACES IN THE EVENT THE BUILDING

SHOULD SETTLE AND DISTURB THE ORIGINAL CONSTRUCTION.

No one builds a better fire

Field constructed Hearth Extensions should be constructed in accordance with
the minimum dimensions provided in Figure 6.