Top vent - vertical termination no elbow, Two elbows – Heat & Glo Fireplace CRESCENT II User Manual

Page 16

background image

Heat & Glo • Crescent II • 2083-902 Rev. N • 7/09

16

2. Top Vent - Vertical Termination

No Elbow

Figure 5.6

Figure 5.7

Two Elbows

V

1

H

1

V

1

V

2

V

1

= 45 ft. Max. (13.7 m)

RESTRICTOR

PLATE

Note: For vertical venting of 8 feet or higher,
the restrictor plate should be used. The
restrictor is shipped in bottom of fi replace
(secured on right side with a tie strap). Insert
the restrictor plate in center of fl ue. Once
installed in center of fl ue turn the restrictor
plate so it sits on top of fi rebox.

V

1

H

1

Maximum

V

2

V1 + V2 Minimum

One Elbow

2 ft

610 mm

*

*

*

6 in

152 mm

2 ft

610 mm

*

*

*

1 1/2 ft

457 mm

3 ft

914 mm

*

*

*

2 1/2 ft

762 mm

5 ft

1.5 m

*

*

*

3 1/2 ft

1067 mm

7 ft

2.1 m

*

*

*

4 1/2 ft

1.4 m

15 ft

4.6 m

*

*

*

V

1

+ V

2

+ H

1

= 38 ft (11.6 m) Max.

*No specifi c restrictions on this value EXCEPT

V

1

+ V

2

+ H

1

cannot exceed 38 ft (11.6 m)