Hubbell Electric Heater Company WATER HEATER DF User Manual
Page 20
20
RECOMMENDED PERIODIC TESTING
TESTING
ITEM
HOW
OFTEN
COMPLETED
BY
REMARKS
Gauges, monitors and operating log
Daily
Operator
Make visual inspection and record readings
Instrument and equipment settings
Daily
Operator
Make visual check against recommended
specifications
Weekly
Operator
Verify factory settings
Semiannually
Service Tech
Verify factory settings
Firing rate
Annually
Service Tech
Check with combustion test
Flue, vent, stack or outlet dampers
Monthly
Operator
Make visual inspection of linkage; check for
proper operation
Igniter
Weekly
Operator
Make visual inspection, check flame signal
strength if meter-fitted (see "Combustion Safety
Controls")
Fuel valves: pilot and main
(primary and secondary)
Weekly
Operator
Operate burner. Using a manometer or pressure
gauge, check pressure to the burner as required
on rating label.
Pilot and main gas or oil train
Annually
Service Tech
Perform leakage tests - refer to instructions
Combustion safety controls (flame
failure)
Weekly
Operator
Close manual fuel supply for the pilot and main
fuel valve(s); check safety shutdown timing; log
result.
Flame signal strength
Weekly
Operator
With flame signal meter installed, read and log
for both pilot and main flames. Notify service
organization if readings are very high, very low
or fluctuating. Refer to instructions for nominal
values
Pilot turndown test
As required /
annually
Service Tech
Required after any adjustment to flame scanner
mount or pilot burner; verify annually - refer to
instructions.
Low-water fuel cutoff and alarm
Daily/weekly
Semiannually
Operator
Refer to instructions and perform a slow drain
test.
High limit safety thermostat control
Annually
Service Tech
Refer to instructions
Operating thermostat control
Annually
Service Tech
Refer to instructions
Vent draft fan, and air pressure
switches
Monthly
Operator
Refer to instructions
High and low gas pressure interlocks
Monthly
Operator
Refer to instructions
High and low oil pressure interlocks
Monthly
Operator
Refer to instructions
Fuel valve interlock switch
Annually
Operator
Refer to instructions
Low fire start interlock
Annually
Operator
Refer to instructions
Automatic changeover control (dual
fuel)
At least
annually
Service Tech
Under supervision of gas utility
T&P valves
As required
Operator
In accordance with procedure in Section VI
ASME Boiler and Pressure Vessel Code,
Recommended Rules for Care and Operation of
Heating Boilers.
Inspect Burner Components
Semiannually
Operator
Refer to burner instructions