27 Room Air Conditioner

Troubleshooting Guide

COMPLAINT

CAUSE

REMEDY

Check the position of knob If not at the coldest set-
ting, advance the knob to this setting and restart
unit.
Check continuity of the thermostat. Replace ther-
mostat if circuit is open.

Check the capacitor.
Replace if not within ±10% of manufacturers rat-
ing. Replace if shorted, open, or damaged.

Check the compressor for open circuit or ground. If
open or grounded, replace the compressor.

Check the compressor overload, if externally
mounted. Replace if open. (If the compressor tem-
perature is high, remove the overload, cool it, and
retest.)

Check the voltage.
If not within limits, call an electrician.

Check overload, if externally mounted.
Replace if open. (If the compressor temperature is
high, remove the overload, cool, and retest.)

If not running, determine the cause. Replace if
required.

Remove the cabinet. inspect the interior surface of
the condenser; if restricted, clean carefully with a
vacuum cleaner (do not damage fins) or brush.
Clean the interior base before reassembling.

If condenser fins are closed over a large area on
the coil surface, head pressures will increase,
causing the compressor to overload. Straighten
the fins or replace the coil.

Test capacitor.

Check the terminals. If loose, repair or replace.

Check the system for a restriction.

If restricted, clean of replace.

Close if open.

Determine if the unit is properly sized for the area
to be cooled.

Check the set screw or clamp. If loose or missing,
correct. If the blower or fan is hitting air guide,
rearrange the air handling parts.

Remove the cabinet carefully and rearrange tubing
not to contact cabinet, compressor, shroud, and
barrier.

Set the knob to HIGH COOL or LOW COOL while

rocker switch is ON.

Check terminals. If loose, repair or replace.

Check the synchronous motor for open circuit.

Thermostat

Capacitor (Discharge
capacitor before servicing.)

Compressor

Overload

Voltage

Overload

Fan motor

Condenser air flow restric-
tion

Condenser fins (damaged)

Capacitor

Wiring

Refrigerating system

Air filter

Exhaust damper door

Unit undersized

Blower or fan

Copper tubing

Rotary switch.

Wiring

Synchronous motor.

Compressor will not run,
but fan motor runs.

Compressor cycles on
overload.

Compressor cycles on
overload.

Compressor cycles on
overload.

Insufficient cooling or heat-

ing

Excessive noise

Auto air-swing fails.