8. electrical service guide – Hobart Welding Products CYBERSTICK OM-314 User Manual
Page 17
OM-314 Page 13
2-8.
Electrical Service Guide
60 Hertz Models
With Power Factor Correction
Without Power Factor Correction
Input Voltage
200
230
460
575
200
230
460
575
Input Amperes At Rated Output
78
68
34
27
103
90
45
36
Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes
125
100
50
40
150
125
70
50
Min Input Conductor Size In AWG/Kcmil
8
8
12
14
6
8
10
12
Max Recommended Input Conductor Length
In Feet (Meters)
61 (19)
80 (25)
131
(40)
133
(40)
87 (27)
77 (23)
208
(64)
200
(61)
Min Grounding Conductor Size In AWG/Kcmil
8
8
12
14
6
8
10
12
Reference: 1993 National Electrical Code (NEC)
S-0092-J
50 Hertz Models
With Power Factor Correction
Without Power Factor
Correction
Input Voltage
220
260
380
440
520
220
380
440
Input Amperes At Rated Output
68
57
39
34
29
84
49
42
Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes
100
90
60
50
45
125
70
60
Min Input Conductor Size In AWG/Kcmil
8
8
10
12
12
8
10
10
Max Recommended Input Conductor Length
In Feet (Meters)
79 (24)
110 (33)
157
(48)
128
(39)
179
(55)
76 (23)
153
(47)
205
(63)
Min Grounding Conductor Size In AWG/Kcmil
8
8
10
12
12
8
10
10
Reference: 1993 National Electrical Code (NEC)
S-0092-J