D896 AUTOMATIC VENT DAMPER

68-0186

3

NOTE:

A minimum of a 30 VA transformer must be used
when D896 is installed with S86/S8600/S8610/
S8620.

Electrical Connections:
Four-wire plug receptacle.

Thermostat Anticipator Setting:
0.13A.

Operating Times:

Approximate Damper Opening Time: 30 seconds.
Approximate Damper Closing Time: 30 seconds.

Temperature Ratings:

Minimum Ambient: 32

°

F (0

°

C).

Maximum Ambient: 150

°

F (66

°

C).

Maximum Furnace Stack: 575

°

F (302

°

C).

Shipping: -20

°

F to +120

°

F (-29

°

C to +49

°

C).

Mounting: See Fig. 2.

Vertical Stack: Any orientation.
Horizontal Stack: The damper actuator must be on the left

or right side of the vent.

IMPORTANT

Do not mount the vent damper with the actuator
above or below the vent.

Dimensions:

See Fig. 1.

DIA

A

DIA

B

DIM.

G

DIM.

H

1 (32)

1
4

2

3
4

DIA

C

4 (116)

9

16

DIM.

D

3 (98)

7
8

7/8 DIA. STD. KNOCKOUT (3)
(ONE, OPPOSITE SIDE)

4 (102)

5 (127)

6 (152)

7 (178)

8 (203)

9 (229)

10 (254)

11 (279)

12 (305)

3 15/16 (100)

4 15/16 (125)

5 15/16 (151)

6 15/16 (176)

7 15/16 (202)

8 15/16 (224)

9 15/16 (252)

10 15/16 (278)

11 15/16 (303)

1 9/16 (40)

1 9/16 (40)

1 9/16 (40)

3 3/16 (81)

3 3/16 (81)

3 3/16 (81)

5 3/16 (132)

5 3/16 (132)

5 3/16 (132)

4 1/2 (114)

4 1/2 (114)

4 1/2 (114)

7 1/2 (191)

7 1/2 (191)

7 1/2 (191)

11 1/2 (292)

11 1/2 (292)

11 1/2 (292)

4 (102)

5 (127)

6 (152)

7 (178)

8 (203)

9 (229)

10 (254)

11 (279)

12 (305)

4 1/16 (103)

5 1/16 (129)

6 1/16 (154)

7 1/16 (179)

8 1/16 (205)

9 1/16 (230)

10 1/16 (256)

11 1/16 (281)

12 1/16 (306)

6 (152)

6 (152)

6 (152)

9 (229)

9 (229)

9 (229)

13 (330)

13 (330)

13 (330)

6 3/4 (171)

7 1/4 (184)

7 3/4 (197)

8 1/4 (209)

8 3/4 (222)

9 1/4 (235)

9 3/4 (248)

10 1/4 (260)

10 3/4 (274)

8 7/8 (225)

9 7/8 (251)

10 7/8 (276)

11 7/8 (301)

12 7/8 (327)

13 7/8 (352)

14 7/8 (378)

15 7/8 (403)

16 7/8 (428)

M11381

DIM. F

DIM. E

(70)

BODY SIZE

(REF)

DIA. A

in. (mm)

DIA. B

in. (mm)

DIA. C

in. (mm)

DIM. D

in. (mm)

DIM. E

in. (mm)

DIM. F

in. (mm)

DIM. G

in. (mm)

DIM. H

in. (mm)

Approvals:

American Gas Association Certified:

Certificate No. U-66-2A1.

Canadian Gas Association Design Certified:

1029AVD-9081.

Replacement Parts:

Damper Actuator is field replaceable without removing the

damper assembly from the stack.

197516A Wiring Harness is a 4-wire cable, 8 feet (2.5

meters) long, with D896 mating plug on one end and
mating plug for S86/S8600/S8610/S8620 or Penn Baso
G60 or G66 on the other. An outlet box connector is on
each end.

APPLICATION

The D896 Automatic Vent Damper is a 24 Vac, motorized
stack damper. The damper closes off the furnace or boiler
stack during the heating off-cycle. Use the D896 only on
Underwriters Laboratories Inc. listed and American Gas
Association design certified atmospheric type, gas-fired
furnaces and boilers. The furnaces or boilers must be
equipped with a draft hood that has an outlet area no larger
than the damper inlet area. Do

not use with oil-fired furnace

or boiler, power burner, or direct vent furnace or boiler.

Fig. 1. Installation dimensions in in. (mm).