OPERATION

Forced Output

The forced output function should only be used by personnel who are
knowledgeable regarding UPS battery string operation. Follow the
instructions in the UPS battery owner’s manual.

The DC voltage selector switch must be set equal to the voltage of the
UPS battery string. Incorrectly setting the voltage selector switch may
cause damage or fire to the UPS battery string. The engine must be
stopped whenever you change the DC voltage selector switch.

Forced output can only be initiated if the DC output does not initiate
automatically when following the ‘‘STARTING THE ENGINE/DC
OPERATION’’ procedure (see pages

).

In addition, the forced output function is dependant on the UPS
battery voltage string voltage. Forced output can only be initiated if
the conditions shown in the following table are met.

Applicable conditions:
Output voltage depends on the DC voltage selector switch position.
Forced output is allowed under the following conditions.

DC Voltage

Selector switch

36 V
48 V

Output indicator

(Green)

OFF
OFF

Overload indicator

(red)

FLASH
FLASH

UPS battery

Voltage

2

27 V

2

42 V

23

25