C7650A SOLID STATE TEMPERATURE SENSOR

63-2499—1

3

L1
(HOT)

L2

1

1

TR1

TR

+

+

+

5

2

4

T1

P1

SO

SR

1

3

T

P

S

620 OHM
RESISTOR

C7650A OUTDOOR
AIR TEMPERATURE
SENSOR

A

B

C

D

TEMPERATURE
SETPOINT

OPEN

MINIMUM
POSITION

MINIMUM
POSITION

24 Vac

MIXED AIR
SENSOR

TR

TR1

TR

TR1

TR

TR1

SEE W7459 SPECIFICATIONS FOR ADDITIONAL
WIRING INFORMATION.

W7459 ECONOMIZER PACKAGE MOUNTED ON ACTUATOR

W7459 ECONOMIZER PACKAGE

ACTUATOR

M7577

Fig. 2. Wiring Connections for C7650A Temperature Sensor.

CAUTION

1. Before beginning installation, disconnect power

supply to prevent electrical shock or equipment
damage.

2. When selecting the location, make sure the

sensor is not exposed to rain, snow, or direct
sunlight.

Location

The C7650A Temperature Sensor can be mounted in any
position; however, the sensor must be installed where it is
exposed to freely circulating air, but protected from rain and
direct sunlight.

The C7650A is designed to operate in 500 ft/min minimum
airflow.

Wiring

Disconnect power supply before beginning installation to
prevent electrical shock or equipment damage. All wiring
must comply with applicable codes and ordinances. Follow
the wiring information furnished by the equipment
manufacturer or refer to Fig. 2 for typical wiring hookups.

OPERATION

Control Dial Setting

Control setpoint scale is located on the W7459 Solid State
Economizer Control. Control points A, B, C, D are field
selectable; use A, B, C, D control points for temperature
sensing.

Operation

The C7650A Solid State Temperature Sensor is used with a
solid state economizer control and damper actuator to
proportion an outdoor air damper in a ventilation system.

When outdoor air temperature is higher than return air
temperature, the outdoor air damper closes to the minimum
position. When the outdoor air temperature and the return air
temperature are equal, the outdoor air damper proportions
open on a call for cooling.

The relationship between the C7650A output current and the
temperature is shown in Fig. 3.

Fig. 3. C7650A Temperature Sensor Output Current.

40

45

50

55

60

65

70

75

80

85

90

95

100

19

18

17

16

15

14

13

12

11

10

9

LED OFF

LED OFF

LED OFF

LED OFF

LED ON

LED ON

LED ON

LED ON

D

C

B

A

mA

DEGREES FAHRENHEIT

NOTE: A,B,C,D ARE W7459A SWITCHING SETPOINTS.

M7578A