Page 8

background image

For technical questions, please call 1-800-444-3353.

SKU 38123

Page 8

3.

The smaller the gauge number of the wire, the greater the capacity of the cord. For
example, a 14 gauge cord can carry a higher current than a 16 gauge cord.
(See Figure C.)

4.

If using more than one extension cord to make up the total length, make sure each cord
contains at least the minimum wire size required. (See Figure C.)

5.

If you are using one extension cord for more than one tool, add the nameplate amperes
and use the sum to determine the required minimum cord size. (See Figure C.)

6.

If you are using an extension cord outdoors, make sure it is marked with the suffix
“W-A” (“W” in Canada) to indicate it is acceptable for outdoor use.

7.

Make sure your extension cord is properly wired and in good electrical condition. Always
replace a damaged extension cord or have it repaired by a qualified electrician before
using it.

8.

Protect your extension cords from sharp objects, excessive heat, and damp or wet
areas.

RECOMMENDED MINIMUM WIRE GAUGE FOR EXTENSION CORDS*

(120 VOLT)

NAMEPLATE

AMPERES

(At Full Load)

EXTENSION CORD LENGTH

25

Feet

50

Feet

75

Feet

100

Feet

150

Feet

0 – 2.0

18

18

18

18

16

2.1 – 3.4

18

18

18

16

14

3.5 – 5.0

18

18

16

14

12

5.1 – 7.0

18

16

14

12

12

7.1 – 12.0

18

14

12

10

-

12.1 – 16.0

14

12

10

-

-

16.1 – 20.0

12

10

-

-

-

* Based on limiting the line voltage drop

to five volts at 150% of the rated amperes.

FIGURE C

Double Insulated

Canadian Standards
Association

Underwriters Laboratories,
Inc.

V ~

Volts Alternating Current

A

Amperes

no

xxxx/min.

No Load Revolutions per
Minute (RPM)

SYMBOLOGY

FIGURE D