50 Hz Performance

Model

Capacity

BtUH/

watts

6°C tD

-9°C SSt

Fan Data

Standard Motor Data

Defrost Heaters (Std.)

HP

total amps

Watts

total amps

CFM/

m

3

h

no. Dia.

in./

mm

air throw ft./

m

0/1/50

380/1/50

380

/3/50

380

/1/50

Standard

w/

Collar

Wired

1-Phase

Wired

1-Phase

Wired

3-Phase

BHg Models 6 Fins Per inch

BHG450 41,400

1,100

8,100

3,400

2 24

610

60

18

80

4

1/2*

6.4

3.4

-

2.6

1,430

3.8

BHG550 50,600

14,800

8,100

3,400

2 24

610

60

18

80

4

1/2*

6.4

3.4

-

2.6

1,430

3.8

BHG640 58,900

17,300

11,300

3,700

3 24

610

60

18

80

4

1/2*

9.6

-

3.0

3.9

1,840

4.9

BHG740 68,100

19,900

11,300

3,700

3 24

610

60

18

80

4

1/2*

9.6

-

3.0

3.9

1,840

4.9

BHG810 74,500

1,800

15,100

43,800

4 24

610

60

18

80

4

1/2*

12.8

-

4.7

5.2

2,730

7.2

BHG950 87,400

5,600

15,100

43,800

4 24

610

60

18

80

4

1/2*

12.8

-

4.7

5.2

2,730

7.2

BHG1020 93,800

7,500

18,600

53,900

3 30

76

90

7

100

30

1

-

-

-

6.9

2,730

7.2

BHG1200 110,400

3,300

18,600

53,900

3 30

76

90

7

100

30

1

-

-

-

6.9

2,730

7.2

BHG1390 127,900

37,500

21,900

63,00

3 30

76

90

7

100

30

1-1/2

-

-

-

9.9

2,730

7.2

BHG1650 151,800

44,500

23,900

69,000

3 30

76

110

34

130

40

1-1/2

-

-

-

10.5

2,870

7.5

BHG2120 195,000

57,100

31,900

9,100

4 30

76

110

34

130

40

1-1/2

-

-

-

14.0

4,230

11.1

BHF Models 4 Fins Per inch

BHF400 36,800

10,800

8,500

4,500

2 24

610

60

18

80

4

1/2*

6.4

3.4

-

2.6

1,430

3.8

BHF480 44,200

1,900

8,500

4,500

2 24

610

60

18

80

4

1/2*

6.4

3.4

-

2.6

1,430

3.8

BHF560 51,500

15,100

11,900

34,300

3 24

610

60

18

80

4

1/2*

9.6

-

3.0

3.9

1,840

4.9

BHF650 59,800

17,500

11,900

34,300

3 24

610

60

18

80

4

1/2*

9.6

-

3.0

3.9

1,840

4.9

BHF710 65,300

19,100

15,900

45,700

4 24

610

60

18

80

4

1/2*

12.8

-

4.7

5.2

2,730

7.2

BHF840 77,300

,600

15,900

45,700

4 24

610

60

18

80

4

1/2*

12.8

-

4.7

5.2

2,730

7.2

BHF890 81,900

4,000

19,500

56,00

3 30

76

90

7

100

30

1

-

-

-

6.9

2,730

7.2

BHF1050 96,600

8,300

19,500

56,00

3 30

76

90

7

100

30

1

-

-

-

6.9

2,730

7.2

BHF1220 112,200

3,900

22,700

65,500

3 30

76

90

7

100

30

1-1/2

-

-

-

9.9

2,730

7.2

BHF1440 132,500

38,800

24,900

71,800

3 30

76

110

34

130

40

1-1/2

-

-

-

10.5

2,870

7.5

BHF1860 171,100

50,100

33,100

95,800

4 30

76

110

34

130

40

1-1/2

-

-

-

14.0

4,230

11.1

table 8. Models BHg/BHF 50 Hz Hot gas Defrost

* 380/3/50 motors are 3/4 HP

Hot gas drain pan available

Notes: TD = Temperature Difference = (Room temperature - saturated suction temperature)

Saturated Suction Temperature °F

+20

-10

-20

-30

-40

Saturated Suction Temperature °C

-7

-23

-29

-34

-40

Multiply Capacity By

1.15

1.04

1.00

0.90

0.80

Capacity Correction Factors for electric and Hot gas Defrost Units