50 hz performance, Table 8. models bhg/bhf 50 hz hot gas defrost – Heatcraft Refrigeration Products BHG User Manual
Page 11
![background image](/manuals/91089/11/background.png)
11
50 Hz Performance
Model
Capacity
BtUH/
watts
6°C tD
-9°C SSt
Fan Data
Standard Motor Data
Defrost Heaters (Std.)
†
HP
total amps
Watts
total amps
CFM/
m
3
h
no. Dia.
in./
mm
air throw ft./
m
0/1/50
380/1/50
380
/3/50
380
/1/50
Standard
w/
Collar
Wired
1-Phase
Wired
1-Phase
Wired
3-Phase
BHg Models 6 Fins Per inch
BHG450 41,400
1,100
8,100
3,400
2 24
610
60
18
80
4
1/2*
6.4
3.4
-
2.6
1,430
3.8
BHG550 50,600
14,800
8,100
3,400
2 24
610
60
18
80
4
1/2*
6.4
3.4
-
2.6
1,430
3.8
BHG640 58,900
17,300
11,300
3,700
3 24
610
60
18
80
4
1/2*
9.6
-
3.0
3.9
1,840
4.9
BHG740 68,100
19,900
11,300
3,700
3 24
610
60
18
80
4
1/2*
9.6
-
3.0
3.9
1,840
4.9
BHG810 74,500
1,800
15,100
43,800
4 24
610
60
18
80
4
1/2*
12.8
-
4.7
5.2
2,730
7.2
BHG950 87,400
5,600
15,100
43,800
4 24
610
60
18
80
4
1/2*
12.8
-
4.7
5.2
2,730
7.2
BHG1020 93,800
7,500
18,600
53,900
3 30
76
90
7
100
30
1
-
-
-
6.9
2,730
7.2
BHG1200 110,400
3,300
18,600
53,900
3 30
76
90
7
100
30
1
-
-
-
6.9
2,730
7.2
BHG1390 127,900
37,500
21,900
63,00
3 30
76
90
7
100
30
1-1/2
-
-
-
9.9
2,730
7.2
BHG1650 151,800
44,500
23,900
69,000
3 30
76
110
34
130
40
1-1/2
-
-
-
10.5
2,870
7.5
BHG2120 195,000
57,100
31,900
9,100
4 30
76
110
34
130
40
1-1/2
-
-
-
14.0
4,230
11.1
BHF Models 4 Fins Per inch
BHF400 36,800
10,800
8,500
4,500
2 24
610
60
18
80
4
1/2*
6.4
3.4
-
2.6
1,430
3.8
BHF480 44,200
1,900
8,500
4,500
2 24
610
60
18
80
4
1/2*
6.4
3.4
-
2.6
1,430
3.8
BHF560 51,500
15,100
11,900
34,300
3 24
610
60
18
80
4
1/2*
9.6
-
3.0
3.9
1,840
4.9
BHF650 59,800
17,500
11,900
34,300
3 24
610
60
18
80
4
1/2*
9.6
-
3.0
3.9
1,840
4.9
BHF710 65,300
19,100
15,900
45,700
4 24
610
60
18
80
4
1/2*
12.8
-
4.7
5.2
2,730
7.2
BHF840 77,300
,600
15,900
45,700
4 24
610
60
18
80
4
1/2*
12.8
-
4.7
5.2
2,730
7.2
BHF890 81,900
4,000
19,500
56,00
3 30
76
90
7
100
30
1
-
-
-
6.9
2,730
7.2
BHF1050 96,600
8,300
19,500
56,00
3 30
76
90
7
100
30
1
-
-
-
6.9
2,730
7.2
BHF1220 112,200
3,900
22,700
65,500
3 30
76
90
7
100
30
1-1/2
-
-
-
9.9
2,730
7.2
BHF1440 132,500
38,800
24,900
71,800
3 30
76
110
34
130
40
1-1/2
-
-
-
10.5
2,870
7.5
BHF1860 171,100
50,100
33,100
95,800
4 30
76
110
34
130
40
1-1/2
-
-
-
14.0
4,230
11.1
table 8. Models BHg/BHF 50 Hz Hot gas Defrost
* 380/3/50 motors are 3/4 HP
†
Hot gas drain pan available
Notes: TD = Temperature Difference = (Room temperature - saturated suction temperature)
Saturated Suction Temperature °F
+20
-10
-20
-30
-40
Saturated Suction Temperature °C
-7
-23
-29
-34
-40
Multiply Capacity By
1.15
1.04
1.00
0.90
0.80
Capacity Correction Factors for electric and Hot gas Defrost Units