beautypg.com

Montana installation instructions – Hearth and Home Technologies Montana-36 User Manual

Page 17

background image

01/04

4039-150 Rev B

17

MONTANA INSTALLATION INSTRUCTIONS

Note:

Use only a noncombustible material to finish

the face of the fireplace below the level of the front

standoffs. A noncombustible material such as USG

MICORE CV230 Mineral Fiber Board, or USG

DUROCK Cement Board is recommended for this

purpose.

Figure 20 - Air Clearance Around Gas Line

12. Complete the Enclosure

Complete the fireplace enclosure, allowing space for outside

air ducts and gas piping if desired. Electrical wiring should

not come in contact with the fireplace. A minimum clearance

of 1½” must be maintained between the fireplace sides

and the enclosure as well as the fireplace back and the

enclosure. See pages 8 and 9 for framing details.

CAUTION:

When using a gas log set, the fireplace damper

must be set in the fully open position. This en-

sures proper venting of combustion products.

WARNING!

This fireplace was not tested by the fireplace

manufacturer for use with an unvented gas log

heater. To reduce risk of injury, do not install an

unvented gas log heater in this fireplace unless

it has been specifically tested and listed by

Underwriter’s Laboratories Inc. for use in this

specific model fireplace. Unless the unvented gas

log heater is tested and listed for use in this fac-

tory built fireplace, a fire hazard may be created

that can result in a structure fire.

13. Gas Log/Lighter Provisions

Knockouts are provided on both sides of the fireplace to allow

for connection of a certified gas log lighter or a decorative

gas appliance certified or tested for outdoor use, with a

maximum input of 100,000 BTU/hour, incorporating an

automatic gas shut-off device and complying with the

Standard for Decorative Gas Appliances for Installation

in Vented Fireplaces, ANSI Z21.60. The decorative gas

appliance should be installed in accordance with the National

Fuel Gas Code, ANSI Z223.1-1980. The side refractories are

designed to allow ½” iron pipe to pass through. Use a

noncombustible sealant to seal any opening between the gas

pipe and refractory on the inside. Repack the insulation

removed to seal around the gas pipe where it exits the side of

the fireplace. A minimum 1½” air clearance must be provided

around the ½” iron pipe for a minimum of 4 inches beyond

the fireplace. See Figure 20.

CLEARANCES!

A minimum 1½” air clearance must be maintained

at the back and sides of the fireplace assembly ex-

cept at the nailing flange where the clearance is ½”.
Chimney sections at any level require a 2” minimum

air space clearance between the framing and chim-

ney section.