Start-up checklist -21, Start-up checklist – Heatcraft Refrigeration Products H-IM-FP User Manual
Page 20

20
Start-up Checklist
Date of Start-up
Location
CONDENSING UNIT
MODEL #
ELECTRICAL
• Check Compressor Amps for COOLER and
FREEZER compressors. Should match
nameplate.
YES
NO
PIPING
• Is suction line trapped at the Cooler?
YES
NO
• Is suction line trapped at the Freezer?
YES
NO
DRAIN LINES
• Are drain lines sloped properly?
YES
NO
• Is drain line trapped outside the Cooler?
YES
NO
• Is drain line trapped outside the Freezer?
YES
NO
• Is heat tape wrapped along entire length of
the drain line in the Freezer?
YES
NO
• Is heat tape plugged in and heating the drain
line?
YES
NO
INSULATION
• Are Liquid lines fully insulated?
YES
NO
• Are Suction lines fully insulated?
YES
NO
SYSTEM CHECKS
• Check Compressor Superheat for the
COOLER (Should be between 20°F. & 30°F.)
YES
NO
• Check Compressor Superheat for the
FREEZER (Should be between 20°F. & 30°F.)
YES
NO
•Force unit into a Defrost Check heater amps.
Should match nameplate amps.
YES
NO
• Check LPS Time Delay Relays. Should be
set at 1 minute for both the COOLER and
FREEZER.
YES
NO
• Check Low Pressure Switch on FREEZER. Should
be set at 0 psig Cut-out/10 psig Cut-in.
YES
NO
• Did FREEZER and COOLER cycle off on LPS at Set-
point Temperature?
YES
NO
• Is the sight glass free of bubbles?
YES
NO
• Are the COOLER and FREEZER fans at proper
speeds?
YES
NO
• Check system for refrigerant leaks. Are there any
leaks on the COOLER, FREEZER, CONDENSING
UNIT or INTERCONNECTING PIPING?
YES
NO
• Check system piping for unusual vibration or
noise. Is there any unusual vibration or noise on
the COOLER, FREEZER, CONDENSING UNIT or
INTERCONNECTING PIPING?
YES
NO