beautypg.com

Troubleshooting - humidity signal verification, 4 to 20 ma signal – Emerson SL-31080 User Manual

Page 3

background image

SL-31080 Product Specification/Installation Sheet

page 3

6/03 (Rev. 0)

Troubleshooting - Humidity Signal Verification

4 to 20 mA Signal

You will measure the humidity output by placing an ammeter in series with the controller input. The control-

ler input is connected to the terminal marked “Ch1 or Ch2” on the humidity board.
1. Verify the unit is terminated properly using Figure 2 shown below, and set your meter to the “Volts”

setting.

2. Verify you have 24 VDC supplied to the unit by measuring between the “V+” and “GND” terminals at the

sensor, as shown below in Figure 1.

3. Set your meter to “Amps” and measure the output between “Ch1 or Ch2” and the controller input as

shown below in Figure 1.

4. Use the following formula to determine what humidity the sensor is reading:

(mA - 4) / 0.16 = %RH
where mA is the current reading from the ammeter (in mA)

Example:
If the current reading is 16 mA, then:

%RH = (16 - 4) / 0.16

= 12 / 0.16
= 75%

Figure 1 Supply Voltage and 4-20mA Verification

Figure 2 4 to 20 mA Output Connection

Analog Input

ROOM SENSOR

CONTROLLER

GND(-)

V+

Ch1 or

Ch2

GND(-)

V+

Analog Input

GND(-)

V+

Ch1 or

Ch2

GND(-)

V+

ROOM SENSOR

CONTROLLER

V

-

A

+

+

-

POWER SUPPLY

POWER SUPPLY