beautypg.com

Functional specifications, Communication specifications, Software specifications – Emerson Process Management Rosemount User Manual

Page 3: Lcd specifications, Volumetric output flowmeters

background image

Product Specification Sheet

00815-0100-4810, Rev AA
June 2005

3

Functional Specifications

The pressure instrument shall have the
capability to be supplied as mounted directly
on the COP primary when the process
temperature is less than 450°F (232°C).

Differential pressure instruments shall be
capacitance technology-based.

The pressure instrument sensor shall be
hermetically sealed from the external
environment.

The pressure instrument shall have built-in
transient protection.

Communication Specifications

Communication with the flowmeter can occur
via a hand-held device.

Digital communication with the flowmeter shall
be via open protocols (e.g. HART,
FOUNDATION

Fieldbus). Proprietary

protocols are not permitted.

The flowmeter shall allow field upgrading of
communication protocols and the addition of
advanced instrument software functions
without changing the pressure sensor.

Software Specifications

The flowmeter shall contain user definable low
flow cut-off functionality.

The pressure instrument shall be able to fully
communicate with a Microsoft

®

Windows

®

based instrument management software via
an open communication protocol.

It shall be possible to store last calibration date
and next calibration due date in the pressure
instrument memory using a hand held
configurator. This information should be
available on Windows-based instrument
management software.

All instruments shall retain original factory
calibration settings in a permanent memory. It
shall be possible to recall this calibration using
a hand-held communicator.

LCD Specifications

The instrument indicator shall be LCD type. It
shall display the numeric value and also have
a 0-100% scale bar graph corresponding to
the analog output. It shall be possible to
configure the indicator to display more than
one parameter (pressure, scaled output); in
this case the display will toggle / scroll to show
all selected parameters. The indicator will
display all alarms and alerts.

Volumetric Output Flowmeters

A volumetric measurement is ideal for liquid fluid
types.

When the COP is integrated with a differential
pressure instrument for volumetric output, the
flowmeter shall perform as follows:

Within ± 0.75% to ± 0.95% of flow rate,
dependant on beta size.

The vendor shall make independent testing
documentation available demonstrating this
performance.

Functional Specifications

Pressure instrument hardware / software
failure alarm shall be selectable as high, low,
or any user-defined value.

The flowmeter shall have the ability to detect
impulse line plugging or should allow field
upgrading to include this by the addition of an
electronics card.

Software Specifications

The flowmeter shall allow the digital output of
the pressure instrument to be scaled to any
user-defined unit (e.g 0-200 m

3

/hr, 0-9000

gallons/min).

The flowmeter shall allow custom
user-entered digital alerts for both high and
low values for the pressure reading. This
digital alert will not affect the analog output.

Flowmeters for custody transfer will have
hardware and software write protect security.
Hardware security will override software.

LCD Specifications

It shall be possible to remote mount
electronics with a display up to 100 ft (30 m)
from the pressure sensor. These electronics
will allow full configuration of the instrument
via a hand-held communicator.