6 Installation Conditions of UL Standards

To adapt SERVOPACKs to the UL standards, make sure that the following
conditions are met.

• Pollution degree: 2
• Protection class: 10
• Altitude: 1000 m max.
• Tightening torque: Varies*

1

• The end user must use a transient suppressive device on the 24 VDC con-

trol power input of the 400 V main power input type SERVOPACKs to
limit transient overvoltages to 500 V maximum.
(Example: surge absorber, etc.)

• Current capacity: Varies*

2,

*

3

* 1. Use the maximum tightening torque listed in the table of Wire Size and

Tightening Torque for Connectors and for Terminal Screw.

* 2. Install the fuse or circuit breakers listed in the 3.1 Molded-case Circuit

Breaker and Fuse in accordance with the guidelines of NEC.

* 3. The following restrictions apply, depending on the SERVOPACKs used.

SERVOPACK

Model SGDV-

Restrictions

180A, 200A

Available rated current for modeled-case circuit breaker: 40 A or

less

330A

• Available rated current for non-time delay fuse: 70 A or less

• Available rated current for time delay fuse: 40 A or less

• Do not use single wires.

470A, 550A

• Available rated current for molded-case circuit breaker: 60 A or

less

• Available rated current for non-time delay fuse or time delay

fuse: 60 A or less

590A, 780A

• Available rated current for molded-case circuit breaker: 100 A or

less

• Available rated current for non-time delay fuse or time delay

fuse: 100 A or less

(Available rated current for class J non-time delay or faster fuse:

125 A or less)

210D, 260D

• Available rated current for molded-case circuit breaker: 60 A or

less

• Available rated current for non-time delay fuse: 60 A or less

• Available rated current for time delay fuse: 35 A or less

280D, 370D

• Available rated current for molded-case circuit breaker: 80 A or

less

• Available rated current for non-time delay fuse: 125 A or less

• Available rated current for time delay fuse: 75 A or less