Thermo Pride C Premiere Series User Manual
Page 9

G. ELECTRICAL 
 
All wiring must conform to the provisions of local codes or, in the absence of local codes, with the 
provisions of the National Electrical Code, "Latest Edition" and this instruction manual. An equivalent type 
wire must be used if any of the original wire supplied with the unit needs to be replaced. 
 
Reference Table A for unit electrical characteristics. Bring proper service to the unit through a circuit 
breaker or fused disconnect switch, in accordance with local codes. In the case of a single phase 230 VAC 
unit, the neutral wire should be brought to the unit in order to provide ground service. A ground wire must 
be connected to the unit at the screw or pressure connector marked "ground". 
 
The best fuse size is the smallest fuse that will allow the equipment to operate continuously without any 
nuisance trips. This type of fuse will give the equipment maximum protection. A time delay type fuse; such 
as Fustat® or Fusetron®, will prevent nuisance trips due to the starting current (locked rotor amps, LRA).
 
 
 
 
 
All field wiring of hazardous voltages must be routed through conduit to the 7/8” access hole provided in 
the base of the Control Panel. 
 
9