WARNING: The nearest point of the vent cap should be a

minimum horizontal distance of six (6) (1.83m) feet from

any pressure regulator. In case of regulator malfunction, the

six (6) foot (1.83m) distance will reduce the chance of gas

entering the vent cap.

CLEARANCES

GAS SUPPLY (continued)

Pressure Testing of the Gas Supply System

1. To check the inlet pressure to the gas valve, a 1/8" (3 mm) N.P.T.

plugged tapping, accessible for test gauge connection, must be

placed immediately upstream of the gas supply connection to

the appliance.

2. The appliance and its individual shutoff valve must be

disconnected from the gas supply piping system during any

pressure testing of that system at test pressures in excess of

1/2 psig (3.5 kPa).

3. The appliance must be isolated from the gas supply piping

system by closing its individual manual shutoff valve during

any pressure testing of the gas supply piping system at test

pressures equal to or less than 1/2 psig (3.5 kPa).

Attention! If one of the above procedures results in pressures in

excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve,

it will result in a hazardous condition.

1. In selecting a location for installation, it is necessary to provide

adequate accessibility clearances for servicing and proper

installation.

2. Unit is supported by a wall bracket secured to the wall.

3. The minimum clearances from casing to combustible construction

is 36" (914.4 mm) on top, 6" (152 mm) on each side and

4" (102 mm) from the floor or from the top surface of carpeting,

tile or other floor covering and 0" (0 mm) to rear wall.

4. The minimum distance from the center of the vent cap to the

nearest outside corner or obstruction is 24" (610 mm).

5. The minimum wall depth is 4 1/2" (114.3 mm) and the

maximum is 12" (304.8 mm). The use of tubes not supplied

by the manufacturer results in unsatisfactory performance.

The vent terminal of a direct vent appliance, with an input of

50,000 (14.6 KW) BTU per hour or less shall be located at least 9"

(229 mm) from any opening through which flue gases could enter

a building. The bottom of the vent terminal and the air intake shall

be located at least 12" (305 mm) above grade.

The vent terminal of a direct vent appliance, with an input of

10,000 Btu per hour (3 kW) or less shall be located at least 6"

(150 mm) from any air opening into a building, and such an ap-

pliance with an input over 10,000 Btu per hour (3 kW) but not

over 50,000 Btu per hour (14.7 kW) shall be installed with a 9"

(229 mm) vent terminal clearance and the bottom of the vent ter-

minal and the air intake shall be located at least 12" (305 mm)

above grade.

Checking Manifold Pressure

Both Propane and Natural have a pressure regulator attached to

the gas valve. Natural gas models will have a manifold pressure

of approximately 4.0" w.c. (.996 kPa) at the valve outlet with

the inlet pressure to the valve from a minimum of 5.0" w.c.

(1.245 kPa) for the purpose of input adjustment to a maximum of

10.5" w.c. (2.61 kPa). Propane gas models will have a manifold

pressure approximately 10.0" w.c. (2.49 kPa) at the valve

outlet with the inlet pressure to the valve from a minimum of

11.0" w.c. (2.739 kPa) for the purpose of input adjustment to a

maximum of 13.0" w.c. (3.237 kPa).
A 1/8" (3 mm) N.P.T. plugged tapping, accessible for test gauge

connection, is located on the side of the gas pressure regulator.