beautypg.com

Safety information, Electromagnetic compatibility – Precision Digital PD6870 User Manual

Page 8

background image

PD6870 Loop-Powered Process Meter

Instruction Manual

8

Electromagnetic Compatibility

EMISSIONS

EN 61326:2006
Safety requirements for measurement, control, and
laboratory use

– Industrial

Group 1 Class A ISM emissions requirements

Radiated
Emissions

Class A

IMMUNITY

EN 61326:2006
Safety requirements for measurement, control, and
laboratory use

ESD

±4 kV contact,
±8 kV air

RFI

– Amplitude

Modulated

80-1000 MHz @ 10 V/m,
1.4-2.0 GHz @ 3 V/m,
2.0-2.7 GHz @ 1 V/m,
80% AM (1 kHz)

EFT

±2 kV DC mains, ±1 kV other

Telco Surge

±1 kV

CRFI

3 V, 0.15-80 MHz, 1 kHz 80% AM

SAFETY INFORMATION

WARNINGS

Read complete instructions prior to installation and operation of the meter.

Installation and service should be performed only by trained service

personnel. Service requiring replacement of internal components must be
performed at the factory.

Disconnect from supply before opening enclosure. Keep cover tight while

circuits are alive. Conduit seals must be installed within 18" (450mm) of
the enclosure.

Verify that the operating atmosphere of the meter is consistent with the

appropriate hazardous locations certifications.

If the meter is installed in a high voltage environment and a fault or

installation error occurs, high voltage may be present on any lead