beautypg.com

Precision digital corporation, Setup, Conduit installation instructions – Precision Digital PD685 User Manual

Page 2: Mounting instructions, Calibration connections, Decimal point selection, Calibration, Installation, Loop connections, Removing display pcb from the loop

background image

www.predig.com

Precision Digital corPoration

89 October Hill Rd • Holliston MA 01746 USA • Tel (800) 343-1001 • Fax (508) 655-8990

LDS685_C 06/09

Model Pd685 3½ digit NeMA 4X looP-PoWeRed MeteR

SIDE VIEW

Mounting
Holes
Located
Beneath
Cover
Screws

E

F

FRONT VIEW

D

A

C

B

Figure 4

Dimensions and Mounting Information

A: 3.15" (80 mm)

C: 2.36" (60 mm)

E: 2.56" (65 mm)

B: 5.51" (140 mm)

D: 4.72" (120 mm)

F: 0.79" (20 mm)

LO CALIBRATION CONTROL

HI CALIBRATION CONTROL

BALANCE CONTROL
(factory adjust only)

DISPLAY PCB COMPONENT SIDE
(may be removed for bench calibration)

S-

S-

S+
S-

S+

S+

BLACK

RED

LOOP JUMPER

CALIBRATED

CURRENT SOURCE

INPUT SIGNAL PCB
(mounted to base of enclosure)

+

-

DP1
DP2
DP3

Figure 1

Calibrator Connected to

Input Signal PCB

INPUT SIGNAL PCB

LOOP JUMPER

(remove when Display PCB is connected)

TRANSMITTER

POWER
SUPPLY

+

+

-

-

4-20mA

S+

S+

S- S-

Field wiring is
made to the
Input Signal PCB
which is mounted
to the base of
the enclosure.

Figure 2

Control loop Connected

to Input Signal PCB

S+

S-

BLACK

RED

DISPLAY PCB

COMPONENT SIDE

CALIBRATED

CURRENT SOURCE

DP1

DP2

DP3

Figure 3

The Display PCB may be removed from the enclosure

for bench calibration. Loop Jumper must be installed

on Input Signal PCB to maintain loop,

refer to procedures below.

Calibrator Connected to Display PCB

Protect enclosure from exposure to chemical solvents and excessive ultraviolet (UV) light (e.g. sunlight).

NOTE: To prevent damage to electronic components caused by electrostatic

discharge, a grounding strap should be worn when

servicing the display.

Conduit installation instructions

1. Remove the Display PCB from the enclosure

2. Connect ½” conduit fittings to the hole in the enclosure

3. Connect conduit (with attached hubs*) to the enclosure

* Use only conduit hubs that are designed to maintain NEMA 4X or IP ratings.

Note: Please read PD686 Intrinsic Safety Barrier Connections for more information

pertaining to conduit holes.

Mounting instructions

1. Remove the enclosure cover from the base.

2. Insert mounting hardware into mounting holes in enclosure base (see Figure 4).

3. Secure the enclosure base to the mounting surface using the inserted hardware.

4. Re-attach the enclosure cover to the base.

SetuP

Only a calibrated current source and a screwdriver are needed for calibration.

Calibration Connections

To access the input terminals it is necessary to remove the enclosure cover and the

Display PCB. This is done by loosening the four screws on the enclosure cover and

removing the cover. Completely loosen the left screw that holds the Display PCB

to the enclosure and loosen the right screw about four turns so the Display PCB

remains attached to the enclosure. Rotate the Display PCB 90° to gain access to the

Input Signal PCB. Next, connect a calibrated current source as illustrated in Figure 1.

decimal Point Selection

The decimal point jumper array is located in the lower right corner of the Display PCB

next to the display. It is labeled DP1, DP2, DP3. Place a jumper over both pins of DP1

for a display of 199.9, DP2 for 19.99, or DP3 for 1.999.

Calibration

LO and HI calibration controls are located to the left of the display

(see Figure 1). Apply a signal equal to 4 mA and adjust the LO control to display the

desired reading. Apply a signal between 16 and 20 mA and adjust the HI control to

display the desired reading. Complete the calibration procedure by making any minor

adjustments to the LO and HI controls.

installation

Installation of the meter involves removing the Display PCB from its enclosure and

connecting a conduit fitting. Use conduit and fittings (not included) suitable for the

degree of ingress protection required.

Mounting holes are located at each corner of the enclosure. Refer to Figure 4.

loop Connections

Disconnect power to the loop and install the meter as illustrated in Figure 2. Replace

the enclosure cover.

Removing display PCB From the loop

The Display PCB and Input Signal PCB are connected together with one black and

one red wire. The wires are soldered to the Display PCB and connected to a screw

terminal connector on the Input Signal PCB.

To remove Display PCB:

1. Loosen the four screws on the enclosure cover and remove the cover from the

enclosure base.

2. Completely loosen the left-side screw holding the Display PCB to the enclosure.

Loosen the right-side screw four turns so the Display PCB remains secure to the

enclosure.

3. Rotate the Display PCB 90° to gain access to the Input Signal PCB.

4. Install Loop Jumper over both pins to bypass Display PCB and allow the signal to

flow through the Loop Jumper. The display will go off when the jumper is installed.

5. Disconnect the black and red signal wires from the screw terminal connector.

6. Loosen completely the right-side screw and lift Display PCB from the enclosure.

Care should be taken to prevent static electricity from damaging the electronic

circuitry.

7. Restore enclosure cover to the base to prevent contamination of components.

Restoring display PCB to the loop

1. Remove enclosure cover as described in step 1 in the preceding section.

2. Secure Display PCB to enclosure using right-side screw; do not tighten screw to

allow rotation of Display PCB while accessing Input Signal PCB.

3. Connect red wire to S+ terminal and black wire to S- terminal, as shown in Figure 1.

4. Remove Loop Jumper to allow the signal to flow through Display PCB (save push-

on jumper by placing over one pin only).

5. Tighten screws holding Display PCB and install enclosure cover.

Servicing display PCB outside the loop

Two modes of input signal allow the user to remove the Display PCB for service

without interrupting the loop as indicated above and operate the Display PCB at

another location. The loop remains connected to the Input Signal PCB while the

Display PCB is absent for service. The user may operate the Display PCB at another

location by connecting a signal to the S+ and S- wires on the Display PCB as

illustrated in Figure 3.