WCP PHYsICaL dImEnsIons
model
Width “a”
Height “B”
depth “C”
Width “d”
Width “E”
Width “F”
Width “G”
Width “H”
Width “I”
shipping
Wt.
09/12
36½”
14½”
10¾”
32”
9”
24½”
8”
18”
16”
85
15/18
47½”
14½”
10¾”
32”
10”
34½”
8”
18”
27”
115
24/30
57½”
14½”
10¾”
42”
10”
44½”
8”
27”
28”
115
36
57½”
17”
11¼”
42”
10”
44½”
10½”
25”
28½”
115
WCP ELECtrICaL sPECIFICatIons
model #
Volts/HZ/
Phase
Fan
total
amps
min.
Volt
min.
ampacity
(1)
max
Fuse (1)
FLa
HP
09A, 12A
115/60/1
0.64
0.03
0.64
104
0.8
15
09D, 12D
208/230/60/1
0.34
0.02
0.34
197
0.43
15
15A, 18A
115/60/1
1.2
0.083
1.2
104
1.5
15
15D, 18D
208/230/60/1
0.56
0.07
0.56
197
0.7
15
24A, 30A
115/60/1
1.2
0.083
1.2
104
1.5
15
24D, 30D
208/230/60/1
0.56
0.07
0.56
197
0.7
15
(1) If electric heaters are installed, use Min Amp and Max Fuse from Heater Options Chart.
dIsCHarGE aIr sPEEd and FLoW
(230V High speed Fan)
model
CFm
Coil
FPm
throw/Ft.
9/12
310
Dry
960
16
15/18
600
Dry
1412
26
24/30
750
Dry
1400
25
36
750
Dry
1400
25
WCP oBsErVEd
sound VaLuEs
(230V High speed Fan)
model
dba
9/12
48
15/18
51
24/30
54
36
54
WCP ELECtrIC HEat oPtIons
model
Voltage KW
Heater
amps
total
amps
min. Cir.
amps
max
Fuse
9/12
230
3
13.1
13.5
16.8
20
15/18
230
3
13.1
13.6
17
20
24/30
230
5
21.7
22.3
27.9
30
36
230
5
21.7
22.3
27.9
30
ConnECtIons
WCP
Chilled Line
size
drain size
1/2” I.D.
1/2” I.D.
5/8” I.D.
1/2” I.D.
5/8” I.D.
1/2” I.D.
3/4” I.D.
1/2” I.D.