IX. Trouble-Shooting

Each Kooltronic Air Conditioner is engineered for performance and built for reliability. They are designed to
require no routine maintenance other than the cleaning of ambient air filters. If your air conditioner
should require warranty service, please contact Kooltronic. If you require service out of warranty,
we have compiled a trouble-shooting chart to assist your service personnel. If additional assistance
is required contact Kooltronic at (609) 466-3400

.

Problem

Cause

Solution

Unit not Cooling

No Power

Check Power Source and
Electrical Connections

Loss of Refrigerant

Locate and repair leak

Evaporator or Condenser

Replace Motor, Capacitor or

Blower not operating

entire Assembly

Filter clogged

Clean or replace Filter

Clogged Evaporator or

Clean Coil

Condenser Coil

Low Temperature Control

Check sensor wire connections

sensor wires broken

Low Temperature Control

Replace Thermostat or Relay

(Thermostat) defective

when applicable

Failed Compressor

Replace Compressor

Ice on Evaporator Coil

Insufficient Heat Load or Unit

Contact Kooltronic

Oversized for Application

Failed Evaporator Blower

Replace Evaporator Blower
Motor or Assembly

Clogged Evaporator Coil

Clean Coil

Condensate draining

Enclosure not properly sealed

Check and seal all openings

continuously

Excessive opening of Enclosure

Eliminate the frequency of
door opening

Excessive vibration

Defective Motor in Blower

Replace Motor

Defective Wheel in Blower

Replace Wheel

Compressor Loose

Tighten Mounting Bolts

Compressor Inoperative

Low line Voltage

Check Nameplate Voltage
against supply

Loss of Compressor Oil

Replace Compressor

Loss of Refrigerant

Locate and repair leak

Failed Compressor Capacitor

Replace Capacitor

Thermal Overload

Contact Kooltronic

Power interruptions

Allow Compressor time to reset

Refrigerant or Oil leaks

Crack or pin hole in tubing or

Replace tubing or rebraze joint

brazed joint

Condensate on the outside Insufficient Heat Load or Unit

Contact Kooltronic

surface of the Enclosure

oversized for application

13