Table 1. Configuration Mode Parameters (cont.)
Parameter

LCD Message

Description

Default Settings

Manual Battery Test

Manual Bat Test

To initiate a manual battery test, press the

button Battery

Test

twice when “Manual Battery Test” is displayed on the
LCD. During the test the LCD displays ON BATTERY.
The UPS resets the automatic timer after a manual
battery test. The LCD displays “Battery not charged”
when UPS test is requested but the battery is not
fully charged.

Manual UPS Test

Manual UPS Test

To initiate a manual UPS self-test, press the

button

UPS Test

twice. During the test, the LCD displays ON BATTERY.

Site Wiring Fault Alarm

Site Fault Set

Select Enable or Disable. When enabled, the alarm sounds Detect Enable
when the ground connection is missing or the line and
neutral wires are reversed in the wall outlet.

Modem Support

Modem Support

This parameter is reserved for future use, and should not

No Modem Support

be modified by the user.

Number of Extended

Bat Pack Num Set

Select the number of EBMs connected to the UPS:

Extern Pack: 0

Battery Modules

• For 700-1500 VA models, select 0 through 2
• For 2000-3000 VA models, select 0 through 5.
You are prompted to save this setting. Refer to the
documentation that came with your battery pack for
more information.

Communications Lock-

COM Control

For greater levels of security, users may choose to have

Enable

out

Cmds

the UPS disregard shutdown commands that come from
the power management software or other communication
sources.
• When disabled, the UPS does not accept a shut down

command via the communication port, USB port, or
communication slot adapter.

• When enabled, the UPS operates normally in response

to external commands.

You are prompted to save this setting.

Load Segment Control

Load Group Set

Allows manual control of load segments (see “Load

Group 1On 2On

Segments” Section 5.3)
By repeatedly pressing the scroll button, the individual
load segments can be turned on and off.
CAUTION To prevent the unintentional shutdown of
specific load segments, confirm your selection before
pressing the

button.

Manual Bypass

Manual Bypass

This parameter is used to manually place the UPS in

Bypass OFF

GO

Bypass mode.

Configuration Mode

Config Mode Set

This parameter is reserved for future use, and should not

EscapeConfigMode

Setting

be modified by the user. The setting may be toggled
between EscapeConfigMode and Enter ConfigMode. 5.0
It should always be set to EscapeConfigMode.