12.2
Maintenance chart
Regular maintenance is most important for the best performance and safe operation.
Regular
service
period (2)
Remarks
Pre-
operation
check
Every 2
months
or 20h
Every 3
months
or 50h
Every 6
months
or 100h
Every 12
months
or 300h
Item
Performed at every
indicated month or
operating
hour
interval, whichever
comes first.
Engine oil
Check
O
Change
O
O
Air cleaner
Check
O
Clean
O(1)
Sediment cup
Clean
O
Spark plug
Clean-
Adjust
O
Replace
O
Spark arrester
Clean
O
Idle speed
Check-
Adjust
O
Valve clearance
Check-
Adjust
O
Combustion
chamber
Clean
After every 500Hrs.
Fuel tank and filter
Clean
O
Fuel tube
Check
Every 2 years (replace if necessary)
(1) Service more frequently when used in dusty areas.
(2) For commercial use, log hours of operation to determine proper maintenance intervals.
12.3
Engine oil replacement
Old oil, even in small quantities, must be brought to a suitable collection point for disposal. Old
oil may not be disposed of with household rubbish, waste water, or even to nature.
You need a 12 mm screw wrench and a recipient of sufficiant capacity to catch the oil (see oil
tank capacity) This recipient must fit below the oil drain bolt (if necessary raise the generator
horizontally on blocks or bricks)
Place the, preferably warm machine on a level surface (warm up the engine for several
minutes if cold).
Position the recipient below the position of the oil drain bolt
Remove the oil drain bolt. Drain the oil completely. (Fig. 6)