Motor Rotation Test

In this step the motor is checked for proper direction
and operation. This test is to be performed solely
from the digital operator. Apply power to the Z1000
after all the electrical connections have been made
and protective covers have been re-attached. At
this point, D

DO NOT RUN THE MOTOR, the Digital

Operator should display as shown in

Fig. 3.

Fig. 3: Digital Operator

Use precaution, and refer to

Fig.1 or 2, swap any two of the
three output leads to the motor
(U/T1, V/T2 and W/T3). After the
wiring change, repeat

Step 5

and recheck motor direction.

After the power has been turned OFF, wait at least five minutes until the
charge indicator extinguishes completely before touching any wiring, circuit
boards or components.

DANGER

If motor rotation is not correct, power down the drive, wait five minutes and
swap 2 motor leads at the drive output terminals.

!

Next, press to move the cursor one

position to the right and to increase the

frequency reference (d1-01) to 10.00 Hz.

Press to save freq. reference.

The motor should now be operating at low speed

running in the correct forward (clockwise) direction.

Next, press on the Digital Operator.

Digital Operator

turned off.

First Digit

Flashing

Press

Green LED

is blinking.

10.00 Hz

Step

4

Z1000 Quick Setup

Step

5

Check Motor Rotation and Direction

Step

6

Hand / Auto Mode Operation

Page 2 of 2

This step shows how to setup the most important parameters using the Z1000 Quick Setup function. Apply power to the Z1000
after all the electrical connections have been made and the terminal cover has been re-attached. At this point D

DO NOT RUN

THE MOTOR the digital operator should be reading as shown in

Fig. 3

. to the right.

After selecting the Application the Z1000 Quick Setup will display the dedicated application parameters to setup your Z1000

Drive for the selected application. Press to access a parameter, and use to select the digit and use

to change the parameter value.

Press

to save the value.

Press to go to the next parameter to continue the Quick Setup programming.

When Quick Setup is completed press “Home” to exit the Quick Setup menu and go to operation.

Frequently Used Parameters

Press three times until the

digital operator shows the Quick Setting menu.

1.

Press to start the

Quick Setup.

2.

Select Application

3.

Press and use to switch

between applications. Press to select.

Available Applications:
0: General: Basic Drive Operation
1: Fan General: Fan Application without PI Control
2: Fan Application with PI Control
3: Return Fan with PI Control
4: Cooing Tower Fan without PI Control
5: Cooling Tower Fan with PI Control
6: Pump (Secondary) without PI Control
7: Pump with PI Control

Parameter

Default

Value

Description

Comments

A1-06

0

Application Selection

See Application list under step 4.

b1-01 1

Reference Source 1
Speed Control Method

0 = Digital Operator (Adjust Motor Speed from keypad)
1 = Terminals (Speed Pot. / 0 – 10V / 4—20mA)

b1-02 1

Run Source 1 /
Start/Stop Control Method

1 = Terminals (Start/Stop using external contact / switch)
3 = Communication

b1-03

1

Stop Method Selection

0 = Ramp to stop (Motor ramps down at stop command)
1 = Coast to stop (Motor freewheels at stop command)

b5-01

0

PI Mode Selection

0 = Disabled, 1 = Enabled, 3 = Fref + PI

b5-02

2.00

PI Proportional Gain Setting

Only active when b5-01 is set to value greater than 0

b5-03

0.5 sec.

PI Integral Time Setting

Only active when b5-01 is set to value greater than 0

b5-20

1

PI Setpoint Scaling

0 = Hz,1= %, 2 = rpm, 3 = custom (use b5-38, b5-39 and b5-41)

C1-01

30.0 sec.

Acceleration Time

The time it takes to ramp up from 0 to maximum motor speed.

C1-02

30.0 sec.

Deceleration Time

The time it takes to ramp down from maximum motor speed to 0.

d2-01

100.0 %

Frequency Reference Upper Limit

Maximum motor speed allowed (e.g. 100 % = Max rpm)

d2-02

0.0 %

Frequency Reference Lower Limit

Minimum motor speed allowed (e.g. 100 % = Max rpm)

E1-01

*

Input Voltage Setting

Motor nameplate voltage

E2-01

*

Motor Rated Current

Motor nameplate current

H3-09

1

Terminal A2 Signal Level Selection

0 = 0 to 10V, 1 = -10 to 10V, 2 = 4 to 20mA, 3 = 0 to 20mA

H3-10

1

Terminal A2 Function Selection

Predefined signals, see Z1000 User Manual

The Z1000 can be operated in HAND mode when the following actions have been
performed:
·

All parameters are programmed

·

Motor direction has been checked

AUTO MODE

Press the A

AUTO button to put the Z1000 into AUTO mode.

In AUTO mode the Z1000 is capable of starting or stopping based on the Run
Source Selection setting parameter b1-02. (See Step 3 Select Start/Stop
Control Method)

The Speed Command used in AUTO mode is based on the Reference Source
Selection setting parameter b1-01. (See Step 3 Select Speed Method)

HAND MODE

The Z1000 can be operated in AUTO mode when the following actions have been
performed:
·

All parameters are programmed

·

Motor direction has been checked

·

Auto Mode: Reference source selected in parameter b1-01 (See step 3)

·

Auto Mode: Run source selected in parameter b1-02 (See Step 3)

Press to access Hand Speed. Use to change

Hand Speed value. Press to save value.

PRESS HAND BUTTON

PRESS TO TURN OFF

PRESS AUTO BUTTON

PRESS TO TURN OFF

AUTO REFERENCE

LED is blinking

when AUTO mode
is active but AUTO

Run Command is

not active.

YAI Document Number: TM.Z1000.01 05/10/2013 ©2012 Yaskawa America, Inc. - (800) YASKAWA (927-5292) Fax (847) 887-7310 [email protected] www.yaskawa.com