No.

Name

Setting Range

Default

Z3–05

Serial Communications Fault Select

0 to 4

1

Setting 0: Ignore
Setting 1: Alarm
Setting 2: Fault with EF0.

Fault FB14 will display in the operator and an EF0 fault will be sent to the drive.

Setting 3: Fault with EF0 and Open Bypass Contactor K3.

Fault FB14 will display in the operator, an EF0 fault will be sent to the drive, and bypass contactor K3 will be opened.

Setting 4: Alarm and run at preset speed set in Z3-10.

Alarm AL14 will display in the operator.

n

Z3-06: Serial Communications Fault Time Select

Sets the time allowed to elapse since receiving serial communications before triggering a communications fault. A value of

0.0 means to never time out.

No.

Name

Setting Range

Default

Z3-06

Serial Communications Fault Detection Time

0.0 to 99.9 s

2.0 s

n

Z3-07: Serial Communications Receive to Transmit Wait Time

Sets the time to delay a serial communications response to a serial communications command.

No.

Name

Setting Range

Default

Z3-07

Serial Communications Receive to Transmit Wait Time

0 to 99 ms

5 ms

Command message

Response message

Command message

Controller→Bypass

→Bypass

Time

24-bit length Z3-07 setting

Bypass Controller

Controller

Figure 4 Serial Communications Receive to Transmit Wait Time Setting

n

Z3-10: Cable Loss Pre-set Speed

When a serial communicaions fault is detected and Z3-05=4, the value here will become the frequency reference.

No.

Name

Setting Range

Default

Z3-10

Cable Loss Pre-set Speed

0.0 to 60.0 Hz

0.0 Hz

n

Z3-11: Serial Communication Fault Detection Selection

Enables or disables the serial communications fault detection.

No.

Name

Setting Range

Default

Z3-11

Serial Communication Fault Detection Selection

0 or 1

1

Setting 0: Disabled

No communication error detection. Ignore setting in Z3-05.

Setting 1: Enabled

If the bypass does not receive data from the master for longer than the time set to Z3-06, then a FB14 Serial Communicaions

fault will be triggered and the bypass will operate as determined by parameter Z3-05.

4 N2 Setup Parameters

YASKAWA TOEP YAICOM 12A Z1000 Bypass Network Protocol Metasys

®

N2 Technical Manual

11