1 Supplemental Information
YASKAWA ELECTRIC TOEP YEASUP 02 Power Regenerative Unit - RC5 Instruction Manual Supplement
3
1
Supplemental Information
Safety Information
Please add this notice to the list of safety messages found on page 7 of the Power Regenerative Unit - RC5 Instruction
Manual, document number TOEP C710656 01.
Applicable Models
The power regenerative unit models listed in
are affected by this supplement:
Table 1 Applicable Models
Applicable Documentation
The following manuals are available for the Power Regenerative Unit - RC5:
NOTICE
Equipment Hazard
Install adequate branch circuit protection according to applicable codes. Failure to comply could result in
damage to the Power Regenerative Unit - RC5.
The device is suitable for circuits capable of delivering 31,000 RMS symmetrical Amperes, 240 Vac maximum (200 V
class) and 480 Vac maximum (400 V class) or the SCCR rating of the drive to which it is connected--whichever value
is greater.
Voltage Class
Model Number CIMR-R5U
200 V
23P7
2018
25P5
2022
27P5
2030
2011
2037
2015
--
400 V
43P7
4022
45P5
4030
47P5
4037
4011
4045
4015
4055
4018
4075
RC5 Instruction Manual
Yaskawa AC Drive - Power Regenerative Unit - RC5 Instruction Manual
Document No: TOEP C710656 01
RC5 Instruction Manual Supplement
Yaskawa AC Drive - Power Regenerative Unit - RC5 Instruction Manual Supplement
Document No: TOEP YEASUP 02
SUPPLEMENT