Step 5: verify configuration, Rosemount 3051s – Emerson 3051S User Manual
Page 13

Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
13
S
TEP
5: V
ERIFY
C
ONFIGURATION
Use any HART-compliant master to communicate with and verify
configuration of the 3051S. For the HART Diagnostics transmitter
(option code DA1), DD revision 3051S HDT Dev. 1 Rev. 1 is required.
A check (
ߛ) indicates the basic configuration parameters. At a
minimum, these parameters should be verified as part of the
configuration and startup procedure.
Table 1. HART Fast Key Sequence
Function
Fast Key Sequence
Alarm Level Configuration
1, 4, 2, 7, 7
Alarm and Saturation Levels
1, 4, 2, 7
Analog Output Alarm Direction
1, 4, 2, 7, 6
Analog Output Trim
1, 2, 3, 2
Burst Mode On/Off
1, 4, 3, 3, 3
Burst Options
1, 4, 3, 3, 4
ߛ Damping
1, 3, 6
Date
1, 3, 4, 1
Descriptor
1, 3, 4, 2
Digital To Analog Trim (4-20 mA
Output)
1, 2, 3, 2, 1
Field Device Information
1, 4, 4, 1
LCD Display Configuration
1, 3, 7
Loop Test
1, 2, 2
Lower Sensor Trim
1, 2, 3, 3, 2
Message
1, 3, 4, 3
Number of Requested Preambles
1, 4, 3, 3, 2
Pressure Alert Configuration
1, 4, 3, 5, 3
Poll Address
1, 4, 3, 3, 1
Poll a Multidropped Transmitter
Left Arrow, 3, 1, 1
Remapping
1, 4, 3, 6
Rerange- Keypad Input
1, 2, 3, 1, 1
Continued on Next Page
4801_QIG_RevHA.fm Page 13 Tuesday, February 26, 2008 12:17 PM