Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes for the drive to be
completely discharged. Measure the DC BUS voltage and verify that it is at a safe level.
Reinstall the operator keypad and terminal cover.
Set parameters n003, n004 and n035 to their appropriate values
Addr
Param
Function
Data
+/- Limits - Description
Default
103h
n003
Operation Method Selection
0 Operator
keypad
1
1 Terminal
2 Serial
Communication
3
Option Card (PROFIBUS-DP Option)
104h n004
Reference
Selection
0
Operator keypad Pot
2
1
Operator keypad
2
Voltage Reference (0-10v)
3
Current Reference (4-20 Ma)
4
Current Reference (0-20 Ma)
5 Pulse
Train
Reference
6 Serial
Communication
7
Multi-Function Analog Input (0-10vdc)
8 Multi-Function
Analog
Input(4-20ma)
9
Option Card (PROFIBUS-DP Option)
123h
n035
Frequency Reference Unit Selection
0
0.01 Hz (< 100hz), 0.1hz (100 Hz
>=100hz)
0
1 0.1%
2-39 Rpm
40-3999 User
Setting
LED Status Indicators and Diagnostics
LED Display
Content
Cause
Counter measures
PWR
COM
ERR
WD
OFF OFF OFF OFF
Power
OFF
Power is not being fed
from the drive.
• Check the main circuit wiring on the
drive.
• Cycle drive power.
Power is not being
provided to the option unit
due to poor option unit
connection.
• Turn of the drive power.
• Check the option unit connection to
the drive.
• Cycle drive power.
Solid
Green
OFF
Solid
Red
Solid
Red
CPU
Error
Option unit CPU error.
• Cycle drive power.
• Replace option unit if fault persists.
Solid
Green
OFF
Solid
Red
Flashing
Red
Drive
Error
Error in Drive unit.
• Cycle drive power.
• Replace drive if fault persists.
Solid
Green
OFF
Flashing
Red
Solid
Green
Com
Error
A fault has occurred
rendering communication
impossible.
• Check whether the address set in
the PROFIBUS-DP Master differs
from the address of the option unit.
• Check that the master is functioning
properly.
• Check that the termination resistor
is correctly connected to the
communication line.
• Check whether the communication
line is correctly connected
(disconnected or poor connection).
• Check that the communication line
is separated from the main power
line.
Solid
Green
Solid
Green
Flashing
Red
Solid
Green
Com
Error
A fault has occurred
rendering communication
impossible.
• Check whether the address is
duplicated with any other devices
within the PROFIBUS-DP network.
Solid
Green
Solid
Green
OFF
Solid
Green
CPU
Init
Option unit under
initialization
• Wait for WD LED to start flashing.
Solid
Green
Solid
Green
OFF
Flashing
Green
Normal
Normal communication
possible.