Yaskawa CM061 User Manual
Page 3

Yaskawa Electric America, Inc –
www.yaskawa.com
IG.AFD.12, Page 3 of 4
Date: 11/17/06, Rev: 06-11
LED Status Indicators and Diagnostics
LED Display
PWR
COM
ERR
WD
Content
Cause
Solution
Option is not powered
• Check the main circuit wiring on the
drive.
• Cycle drive power.
OFF OFF OFF
OFF
Power
OFF
Poor connection to drive
• Turn of the drive power.
• Check the Profibus-DP Option
connection to the drive 2CN connector,
• Cycle drive power.
Solid
Green
OFF
Solid
Red
Solid
Red
CPU
Error
Option unit CPU error
• Cycle drive power.
• Replace Profibus-DP Option if fault
persists.
Solid
Green
OFF
Solid
Red
Flashing
Red
Drive
Error
Error in Drive unit
• Cycle drive power.
• Replace Profibus-DP Option if fault
persists.
• Replace drive if fault persists.
Solid
Green
OFF
Flashing
Red
Solid
Green
Com
Error
Communication Failure
• Check whether the address set in the
Profibus-DP Master differs from the
address of the option unit.
• Check that the master is functioning
properly.
• Check that the termination resistor is
correctly connected to the
communication line.
• Check whether the communication line
is correctly connected (disconnected or
poor connection).
• Check that the communication line is
separated from the main power line.
Solid
Green
Solid
Green
Flashing
Red
Solid
Green
Com
Error
Communication Fault
• Check whether the address is duplicated
with any other devices on the Profibus-
DP network.
Solid
Green
Solid
Green
OFF
Solid
Green
CPU
Init
Initialization
• Wait until WD LED is flashing
Solid
Green
Solid
Green
OFF
Flashing
Green
Normal Normal
Profibus-DP Configuration
To simplify the drive configuration, the GSD file can be obtained at
www.yaskawa.com
. Select Downloads, By Inverter Drives, By
Product, and Network Comms-Profibus. Then select the file named
YASK00CA.GSD.
Load the GSD file, YASK00CA.GSD, into the proper directory for the
configuration tool used. Retrieve the GSD file form either
www.yaskawa.com
or
www.profibus.org
to make sure that the latest
GSD file is loaded.
Select the Profibus-DP INTER device when adding Yaskawa drives to
the Profibus configuration. See the figure to the right.
The Profibus-DP Option Card supports three configuration options:
Extended Data 1 (32 words of input and output), Extended Data 2 (12
words of input and output) and Basic Data (3 words of I/O). Refer to the
Profibus-DP Option Technical Manual (TM.AFD.12) for further
information on each configuration. See the figure to the right.