Yaskawa G5 OV Suppression User Manual
Page 5

Date: 07/01/04, Rev: 04-07
Page 5 of 8
TM.G5SW.017
New Program Parameters
P1-01
DC Filter Rise amount per scan
B
B B B
DC Filter Rise
P1-01= 0.01 Vdc
The DC Filter Rise amount will be added to the DC bus filter when the DC bus voltage
exceeds the value of the DC bus filter + P1-03: Deadband. This value will be added at
a rate of 20 times a second. Using the default value results in a rate of 0.20 Vdc per
second.
P1-02
DC Filter Fall amount per scan
B
B B B
DC Filter Fall
P1-02= 0.50 Vdc
The DC Filter Fall will be subtracted from the DC bus filter when the DC bus voltage is
below the value of the DC bus filter - P1-03: Deadband. This value will be subtracted at
a rate of 20 times a second. Using the default value results in a rate of 1.00 Vdc per
second.
P1-03
DC Filter Deadband amount
B
B B B
Filter Deadband
P1-03= 10.0 Vdc
The dead band is the +/- amount that the DC bus must change before the DC bus filter
will be changed. This parameter provides a means of preventing OVP corrections for
normal DC bus fluctuations.
Setting Range:
0.00 to 1.00 Vdc
Factory Default:
0.01
Modbus Address:
0x580
Setting Range:
0.00 to 1.00 Vdc
Factory Default:
0.50
Modbus Address:
0x581
Setting Range:
0.0 to 99.0 Vdc
Factory Default:
10.0
Modbus Address:
0x582