2 Overvoltage Suppression A1000 Custom Software

YASKAWA TM.A1000SW.062 Overvoltage Suppression A1000 Custom Software Supplement

9

Table 4 Additional Function Text

Table 5 Monitors U1-††

Table 6 Multi-Function Input Settings H1-††

P2-01

060Ah

Belt Break Detection

Belt Break Det

This parameter configures the Belt Break

Detection function. If the drive's soft starter

is at maximum output frequency (E1-04) for

more than 30 seconds, a belt break fault (B-

BRK) will occur.

0: Disabled

1: Enabled

0 to 1

1

No

– – – – Y – Y

Function: Torque Ramp During Start

P3-01

0614h

Torque Limit During Start

Start Torque

This parameter determines the forward and

reverse motoring torque limits after a run

command is received, but before the torque

start timer (P3-02) expires. This parameter

overwrites L7-01 and L7-02.

0 to 300

200 %

No

– – – – Y – –

P3-02

0615h

Torque Limit During Start

Timer

Start Torq Time

This parameter sets the time that parameter

P3-01 will overwrite L7-01 and L7-02 after

a run command is received.

0.0 to 10.0

0.0 sec

No

– – – – Y – –

P3-03

0616h

Torque Limit During Start

Ramp Time

Torq Lim Ramp Tm

This parameter sets the time required to

ramp the torque limit 100%. This

determines the rate at which the torque

limits will return to the L7-01 and L7-02

values at the end of the starting torque time

(P3-02).

0.1 to 10.0

1.0 sec

No

– – – – Y – –

<1> The response of this parameter will be affected by drive size. If a drive is replaced with one of a different size (current rating), this parameter may need

adjustment.

<2> Making large changes in these settings while the drive is running can result in large and very rapid changes in the output frequency.

Change these parameters in small increments only.

Function No.

Function Name

Digital Operator Display

P

(Function group)

Overvoltage Suppression

OV Suppression

P1

Overvoltage Suppression

OV Suppression

P2

Belt Break

Belt Break

P3

Torque Limit During Start

Torque Dur Start

U7

Overvoltage Suppression

OV Suppression

Monitor No.

MEMOBUS/

Modbus

Address

Monitor Name

Digital Operator

Display

Description

Analog output

scaling

Unit

Control Method/

Access Level

U7-02

0661h

Soft Start Frequency

Reference

Soft Start Freq

Displays the frequency reference after the soft starter,

but before the OV Regulator PI controller output.

100% =

Fmax (E1-04)

0.01 Hz

– – – – Y – Y

U7-03

0662h

Overvoltage Frequency

Reference

OV Reg Total Ref

Displays the frequency reference after the output of the

OV Regulator PI controller.

100% =

Fmax (E1-04)

0.01 Hz

– – – – Y – Y

U7-04

0663h

Overvoltage Suppression

Regulator Error Signal

OV Reg Error

Displays the error (setpoint - feedback) of the OV

Regulator PI controller.

100% =

Motor Rated

Torque (Iq)

0.1 %

– – – – Y – Y

U7-05

0664h

Overvoltage Suppression

Regulator Output

OV Reg Output

Displays the output of the OV Regulator PI controller.

100% =

Fmax (E1-04)

0.1 %

– – – – Y – Y

Setting

Description

Control Method/

Access Level

80

OVS Disable

Closed: Disables the OV Suppression function if OV Suppression is enabled (P1-01=1).

Note: If this input is opened while OV Suppression is running, the drive will ramp the OV

Suppression regulator setpoint from -100% to P1-02 at a fixed rate of 122% / second to prevent

irregularities in motor operation.

– – – – Y – Y

No.

MEMOBUS/

Modbus

Address

Name

Digital Operator Display

Description

Range

Default

Value

Change

During

Run

Control

Method/

Access Level