Chs controls ab – Eaton Electrical MN05401014E User Manual
Page 3
![background image](/manuals/80130/3/background.png)
MN05401014E
3
english
5. Technical data
Supply voltage:
DC power supply:
10 – 30V DC/max. 40 mA
Display:
6 digits, red 7 segment
LED display, height 8 mm
[0.31 in.]
Data retention:
EEPROM
Polarity of the inputs:
Programmable, npn or pnp
(sinking or sourcing) for all
inputs
Input resistance:
appr. 5 kOhm
Count frequency:
Minimum pulse length for the reset input:
5 ms
Input sensitivity:
Standard sensitivity:
DC power supply:
Low: 0 – 0.2 x UB [V DC]
High: 0.6 x UB – 30 [V DC]
UB = Supply Voltage
Pulse shape:
any*,
Schmitt Trigger inputs
Ambient temperature:
-20 to +65°C [-4 to 149°F]
Storage temperature:
-25 to +70°C [-9 to 158°F]
EMC:
In compliance with the EC Directive
2004/108/EEC
Noise emission:
EN 61 000-6-3/
EN 55 011 Class B
Noise immunity:
EN 61 000-6-2
* at maximum frequency (50-50 duty cycle)
Housing:
For front panel mounting
48 x 24 mm
[1.89 x 0.94 in.]
acc. to DIN 43700,
RAL 7021, dark grey
Weight:
appr. 50 g [1.76 oz.]
Front panel rating: IP 65
Cleaning:
The front of the units is to be cleaned only with a
soft cloth moistened with water.
6. Terminal assignment
1 10 – 30V DC
2 0V GND
3 INP
4 –
5 Reset
DC power supply:
24V
12V
Input level:
Standard
typ. low level:
2.5V
2.0V
typ. high level:
22.0V
10V
Fmax:*
60 kHz
20 kHz
MN05401014E:MN05401014E 2/9/07 1:27 PM Page 3
CHS Controls AB
Tel +46 42 38 61 00, Fax +46 42 38 61 29
[email protected] www.chscontrols.se