8-12

Instruction Manual

IM-106-340, Rev. 4.0

May 2006

Oxymitter 4000

Figure 8-8. Fault 6, High High Heater Temp

Fault 6, High High Heater Temp

Figure 8-8 shows the electronic assembly for an
Oxymitter 4000 with a membrane keypad (upper
view) and an Oxymitter 4000 with an LOI (lower
view).

Membrane Keypad

When Fault 6 is detected, the HEATER LED
flashes twice, pauses for three seconds, and
repeats.

1. The High High Heater Temp alarm will

activate when the thermocouple produces
a voltage of 37.1 mV [1652°F (900°C)].

2. The triac and the temperature control may

be at fault.

3. Remove power. Allow Oxymitter 4000 to

cool for five minutes. Restore power.

4. If the condition repeats, replace the

electronic assembly per "Electronic
Assembly Replacement" in Section
9:
Maintenance and Service.

LOI

When Fault 6 is detected, the LOI displays the
"Very Hi O2 Temp" message.

1. The very high O2 temperature alarm will

activate when the thermocouple produces
a voltage of 37.1 mV [1652°F (900°C)].

2. The triac and the temperature control may

be at fault.

3. Remove power. Allow the Oxymitter 4000

to cool for five minutes. Restore power.

4. If the condition repeats, replace the

electronic assembly per "Electronic
Assembly Replacement" in Section
9:
Maintenance and Service.

37260024

LOI

KEYPAD

Alarms

Very Hi O2 Temp

DIAGNOSTIC

ALARMS

TEST

POINTS

HEATER T/C

HEATER

O2 CELL

CALIBRATION

CALIBRATION RECOMMENDED

O2 CELL mV +

O2 CELL mv -

HEATER T/C +

HEATER T/C -

INC

INC

DEC

DEC

HIGH

GAS

LOW

GAS

CAL

TEST GAS +

PROCESS -

% O2

SW2

TP1

J1

TP2

TP3

RED

YEL

GRN

ORG

TP4

TP5

TP6

ON